26 of 53
Doc 6001242 (01-20273)
Rev C
D.
MASTER/SLAVE SETUP PROCEDURE
1.
Be sure to turn off both gate operator units.
2.
Connect Master and Slave units as described and shown in paragraph C and Figure 15, above.
3.
Set Switch S1 on Master and Slave units to your gate configuration according to the table, below.
NOTES
•
If, before power up, the Master/Slave connection is broken, one of the units is turned off, or one of
the controller boards malfunctions, the gates will operate in stand alone configuration.
•
If the Master/Slave connection is broken after power up, it prevents either gate from moving.
MASTER
UNIT SWITCH S1 SETTINGS AND INPUTS
Gate
Type
SLIDE
ACTION
(Reclose)
TIMER
RETRY
ATG
MASTER
TRAP
Operator
Inputs
Bi-Parting
Unit
Option
➎
System
Option
n
System
Option
n
System
Option
n
ON ON
System
p
Bi-Parting
Latch
Unit
Option
➎
System
Option
n
System
Option
n
System
Option
n
ON OFF
System
p
Trap
Unit
Option
o
Unit
Option
o
Unit
Option
o
ON ON ON Unit
➍
Tandem
Unit
Option
o
Unit
Option
o
Unit
Option
o
OFF ON ON Unit
➍
n
:
Select ATG, Timer and/or Retry (if desired) from the Master unit and set Slave ATG, Timer and Retry to OFF.
Otherwise, the ATG ON/shorter Reclose Timer/Retry ON in either unit supersedes the other.
o
:
Master and Slave units can have different settings.
p
: I
nputs affect both gate operators, so connect to one unit only.
➍
: I
nputs affect one gate operator only, so connect inputs separately to each gate operator.
➎
:
For safe and reliable operation, this setting MUST be the same for both units (see Appendix A).
SLAVE
UNIT SWITCH S1 SETTINGS AND INPUTS
Gate
Type
SLIDE
ACTION
(Reclose)
TIMER
RETRY
ATG
MASTER
TRAP
Operator
Inputs
Bi-Parting
Unit
Option
➎
System
Option
n
System
Option
n
System
Option
n
ON OFF
System
p
Bi-Parting
Latch
Unit
Option
➎
System
Option
n
System
Option
n
System
Option
n
OFF OFF
System
p
Trap
Unit
Option
o
Unit
Option
o
Unit
Option
o
No Effect
OFF
OFF
Unit
➍
Tandem
Unit
Option
o
Unit
Option
o
Unit
Option
o
Unit
Option
OFF OFF Unit
➍
n
:
Select ATG, Timer and/or Retry (if desired) from the Master unit and set Slave ATG, Timer and Retry to OFF.
Otherwise, the ATG ON/shorter Reclose Timer/Retry ON in either unit supersedes the other.
o
:
Master and Slave units can have different settings.
p
: I
nputs affect both gate operators, so connect to one unit only.
➍
: I
nputs affect one gate operator only, so connect inputs separately to each gate operator.
➎
:
For safe and reliable operation, this setting MUST be the same for both units (see Appendix A).