INITIAL OPERATION

BASIC SETTING

Proceed step by step. If you are not sure, start again at the beginning. Take suf

 cient time to make these settings.

1. Are all components required for operation connected? Motors, photocells, safety contact strip, stop switch.

2. If your installation consists of only 1 gate (wing) the DIP “1 / 2 Motor” must be on (also refer topage 11, DIP SWITCH SETTINGS).

3. Make sure that nobody is present in the range of the gates.

4. Close the gate/s and attach motor/s.

ART:

- Reference point or “passpoint” has to be adjusted to allow

  a successful travel distance programming. The cams under

  the cover of the ART need to be positioned correctly. The top

  cam clicks the micro switch 

 rst and the bottom cam as second.

  The micro-switches pushed by the cam shall not be pushed

  (clicked) at the same time and shall be not pushed in the end

  position of the gate. Twist the cams by using a pair of pliers or

  with a large 

 at screwdriver.

- Disengage the gate using the release key for this adjustment.

- In case the drive arms are, after this installation step, re-located

  the cam position has to be checked if a further adjustment is

  required.

- DIP settings for ART: DIP SPEED off! 

   ART will not work if DIP SPEED is on.

SUB (Underground):

- DIP setting: DIP SPEED on for faster gate movement or off if gate is heavy or safest way of operating is

  required. Can be changed any time later after completion of the installation.

LYN-SCS Operator:

- DIP setting: DIP SPEED on for faster gate movement or off if gate is heavy or safest way of operating is required. 

  Can be changed any time later after completion of the installation.

Now connect the mains supply (230V) to the control board.

BASIC SETTING:

1. Press buttons P1, P2 and P3 simultaneously for approx. 2-3 seconds until yellow LED 

 ashes.

2. Monitor the gate. Press and hold P1 for 1-2 seconds. The wing with motor 1 opens. If motor 1 closes, it is wired 

    incorrectly and the red and blue wires of the motor cable must be reversed. (Caution: Disconnect Power!)

    Repeat steps 1 and 2. Leave gate/s in partially open position.

NOTE: General operation – if you release the button, the gate will immediately stop. By pressing the button again the gate will

move in the opposite direction until you release the button, and so on.

3. Press and hold P2 for 1-2 seconds. The wing with motor 2 must open. (Do not open gate completely, only short

    distances.) If motor 2 closes, it is wired incorrectly and the red and blue wires of the motor cable must be reversed.

    (Caution: Disconnect Power!)

    Repeat steps 1 and 2. Leave gate/s in partially open position.

    NOTE: The control board is active for this manual setting mode for approx. 20 seconds. If necessary, start again by pressing P1,

    P2 and P3 simultaneously.

Now check the following:

1. SCS only: During opening the front housing must not touch the gate. Stop opening several times and check. If housing

    touches the gate dimensions A/B must be checked and if necessary, underlay the gate pillar with 

 at washers in order to

    enlarge clearance.

2. Both wings must open completely. Do not open the wings too far! If there are no stops, choose and mark a position for

    maximum opening.

3. SUB (underground operator) only: Now adjust your hard-stop in the box.

    Wait until learn-LED goes out (20 seconds after a button was pressed).

Closed position

Open position

gate open

gate closed

Summary of Contents for LYN300 Series

Page 1: ...atické pohony bran modely LYN300 LYN400 série SCS300 Instrucciones Automatismos de puerta automáticos modelos LYN300 LYN400 SCS300 de las series O ËÁ Â ÙfiÌ ÙÔÈ ÌË ÓÈÛÌÔ ÁÎ Ú fi ÔÚÙ ÌÔÓÙ Ï LYN300 LYN400 SCS300 Series Útmutatók SCS300 as sorozatba tartozó LYN300 as és LYN400 as automatikus garázsajtó Upute Automatski pogoni vrata modeli LYN300 LYN400 SCS300 serije Istruzioni Automazioni per cancell...

Page 2: ... 2 0 m 3 0 m 4 0 m 5 0 m 6 0 m 250 kg 180 kg 160 kg 140 kg Wing Weight Wing Size LYN300 LYN300 LYN400 LYN400 0 m 0 5 m 1 0 m 1 5 m 2 0 m 2 5 m 3 0 m 250 kg 180 kg 160 kg Wing Weight Wing Size SCS300 3 5 m 4 0 m ...

Page 3: ...6 DESCRIPTION OF LEDS 6 FUNTIONALITY OVERVIEW OF THE PUSH BUTTONS P1 P2 P3 RESET 6 OPTIONAL ACCESSORIES 7 PHOTOCELLS 8 RADIO AND RADIO PROGRAMMING 8 PROGRAM INTERNET GATEWAY my Q DOOR MONITOR 9 LOOP DETECTOR USAGE 10 DIP SWITCH SETTINGS 11 WING DELAY ADJUSTMENT 11 INITIAL OPERATION BASIC SETTING 12 14 TIMER TO CLOSE AUTO CLOSE 14 FORCE TORQUE OF MOTOR 14 DISPOSAL BATTERY DISPOSAL 14 INDICATION OF ...

Page 4: ...o check with your gate manufacturer for an opener installation reinforcement kit Activate opener only when the gate is in full view free of obstructions Do not allow children to play near the gate Humidity and water destroy the control board Make sure under all circumstances that water humidity or dammed up water cannot penetrate the control board covering Frequently examine the installation for i...

Page 5: ...optional Is mounted on the outside The gate is opened by key or by entering a number 7 Contact strip optional Safeguards the gate on being touched Contact strips can be mounted on the gate or on the pillars If required contact strips must be mounted at a height of up to 2 5m 2 16 en CONTROL BOX The control consists of several components exterior installation box 1 cover for box 1 control 1 transfo...

Page 6: ...s C Fasten transformer on to baseplate using the large screw and large washer D Put the 4 large closure screws through cover of the box Fasten 2 of them left or right approx 2cm into the box After that the cover can be opened to the side E Close box on a trial basis turning the screws all the way in If the lid does not close completely then the box is not fitted to the wall evenly and is therefore ...

Page 7: ...h identical colours distribution box IP65 cable screw joints and fastening material 041ASWG 0482 50 Cable 50m for professional use Consists of 50m of cable 6 pole with identical colours Cut only as much as you need for the current installation General wiring sizes The numbers mentioned in the table below are minimum requirements It is always possible to use larger diameters 230Volt Supply Power to...

Page 8: ...CM475 BROWN GREEN WHITE BROWN GREEN WHITE YELLOW YELLOW RADIO MODULE Model 207399 230 VAC 50 RED RED BLUE BLUE BROWN GREEN WHITE BROWN GREEN WHITE not required not required RED RED BLUE BLUE BROWN GREEN WHITE BROWN GREEN WHITE YELLOW YELLOW ART SUB Closed position Open position external battery ...

Page 9: ...D motor 2 Second opens second red blue To check correct polarity refer to section basic setting and functionality P1 P2 P3 RESET 24V 150mA flashing light accessory Motor1 MASTER BRN brown cable GRN green cable WHT white cable YEL yellow cable Motor2 SECOND BRN brown cable GRN green cable WHT white cable YEL yellow cable Light Contact gate monitor yard lighting PED key switch COM negative pole STOP ...

Page 10: ...ith 829EV door monitor allows optical and acoustical monitoring of the gate position The gate can also be closed with the device BACKUP BATTERY OPTIONAL The terminals serve to reload an externally installed storage battery The integrated recharger is loaded and in case of power failure the battery provides power A new fully charged storage battery may provide power for more than 24 hours Storage b...

Page 11: ... LED flashes photocell disables control board Connection between 1 COM Active when gate is closing reverses gate to open Connection between 2 COM Active when gate is closing and opening Connection between 3 COM Active when gate is opening holds gate in present position until photocell is cleared continues when cleared RADIO AND RADIO PROGRAMMING PROGRAM DELETE REMOTE CONTROLS The receiver has two c...

Page 12: ...the LEDs will blink 3 times and go out 7 The App will tell you if programming was successful and will prompt you to assign a name to the gate PROGRAM DOOR MONITOR Using the RESET Button on the control board 1 Connect power to the door monitor Position the door monitor in a convenient visible place inside the house If this place is too far from the gate opener the connection may not be possible or ...

Page 13: ... truck but do not comply with regulations as single protection since they do not detect people The loop detector control board output is wired as NO signal to the 8 2KOhm safety edge output In case you use safety edges as well Check the functionality you need before installation Interrupt loop DIP OPEN STEP must be on Shadow loop DIP OPEN STEP must be off Other options for loop detectors can be re...

Page 14: ...CS SUB RADIO The DIP RADIO is required to program remote controls For programming procedure please refer to page 8 section radio OFF No programming of remote controls possible ON Programming of remote controls possible Important Switch off DIP RADIO if not in use Wing Delay Adjustment The delay of one wing is required to open and close the wings correctly and to operate the wings with a safe dista...

Page 15: ...anged any time later after completion of the installation Now connect the mains supply 230V to the control board BASIC SETTING 1 Press buttons P1 P2 and P3 simultaneously for approx 2 3 seconds until yellow LED flashes 2 Monitor the gate Press and hold P1 for 1 2 seconds The wing with motor 1 opens If motor 1 closes it is wired incorrectly and the red and blue wires of the motor cable must be rever...

Page 16: ...When the learn LED goes out the programming has finished PROGRAMMING TRAVEL DISTANCES ADVANCED NOTE In this mode P1 must be pressed 9 times With every time the button is pressed a position time is stored This allows programming of SOFT STOP slow travel in order to adjust to application Long or short phases of SOFT STOP are possible 1 Both wings must be closed 2 Press P1 and P2 for approx 5 6 second...

Page 17: ...r changes to the installation rust or inappropriate lubrication it may have to be repaired The control board complies with the latest EU guidelines One of these guidelines specifies that the closing forces at the gate edge must not exceed 400N 40 kg for the last 500 mm before the door is CLOSED Above 500 mm the maximum force at the gate edge must not exceed 1400 N 140 kg If this cannot be ensured a...

Page 18: ...nstallation A Object obstructs safety edge B Defective safety edge C Power too low or broken wire in supply Power supply to control board is too low A Defective supply 230V or malfunctioning contact B Broken wire in supply cable copper cable C The battery accessory to operate the gate whilst power failure is dead EEPROM Fault Power up failed Only LYN SCS Release lever OPEN Defect on relay or major...

Page 19: ... 2 Find and rectify fault s see description of diagnostic LEDs 3 Check photocell connection programming 4 Check terminals and connections 1 Program transmitter 2 Check photocells check diagnostic LEDs 3 DIP RADIO must be off Program travel distance See initial operation diagnosis LED re program travel distance consult dealer specialist 1 Check manual especially 1 2 Motor 2 If motor is moving check...

Reviews: