background image

WIRING OF CONTROL / SUMMARY

a) start with 230Volts supply cable.

    Run cable through large cable bushing on the lefthand side.

b) Attach cable eye to ground wire. Then connect ground wire to

    base plate with washer and nut (exactly as shown in picture detail).

    Connect all other cables to control.

CABLES AND WIRING

The usage of shielded cable in order to connect the motor to control board is highly recommended. Magnetic and inductive in

 uence of the signal in

the cables can produce electric noise and may disturb the function of the gate .

Generally avoid:

- Control board location far away from gate.

- 230Volt and low voltage in the same power line. Not allowed by electrical rules.

- Wiring of the infrared sensors, switches, 

 ashing lamps & electric locks require a cable separately from the motor wiring.

- Other wirings like telephone intercoms, lights for garden etc. must be in separate cables.

- Rigid copper cables especially when thicker diameters are dif

 cult to manage during the installation and may result in bad connections with

  functional issues. Use instead 

 exible cables.

- Cable material not suitable for outside use. Use cables suitable for outside use and underground. Run the cables in conduits if the cable is not

  suitable for placing in the ground (armoured or suitably protected). You may also consult your local electrician.

We recommend the following accessories:

- LA400-JB40E Kit for cable extension of one installation unit. Consists of 12m of cable 6-pole with identical colours, distribution box IP65,cable

  screw joints and fastening material.

- 041ASWG-0482-50 Cable 50m for professional use. Consists of 50m of cable 6-pole with identical colours. Cut only as much as you need for the

  current installation.

General wiring sizes:

The numbers mentioned in the table below are minimum requirements. It is always possible to use larger diameters.

- 230Volt Supply Power to controller: min. 0,75mm² 3-pole

- 230Volt Supply transformer installed separately (i.e. in the garage) and low voltage to gate. See table.

- Motor wiring: 2 wires min. 1,0mm², 4 wires min. 0,75mm² (or shielded cable)

- Electric locks: See table

- Switches, infrared sensors, 

 ashing lamp: See table etc. min.0,5mm²

       4/16 en

Operator Model

LYN, SCS, ART

motor wiring

SUB (underground)

motor wiring

Transformer separately

installed (in garage) and

low voltage supplied to

control board box.

Electric lock (12Volt)

wiring

External antenna

(Remove original

antenna of logic board)

Switches, Flashing lamp

etc.

Infrared Sensors

Distance

0m - 6m

2 x 1,0mm²

4 x 0,75mm²

2 x 1,0mm²

3 x 0,75mm²

0,75mm²

0,75mm²

Coax cable (Satellite

cable)

50 Ohm

0,5mm²

0,5mm²

Distance

6m - 10m

2 x 1,0mm²

4 x 0,75mm²

2 x 1,0mm²

3 x 0,75mm²

0,75mm²

0,75mm²

Coax cable (Satellite

cable)

50 Ohm

0,5mm²

0,5mm²

Distance

10m - 12m

Normal

Wiring

Use shielded cable for

the 3 smaller motor wires

1,0mm²

1,0mm²

Coax cable (Satellite

cable)

50 Ohm

0,75mm²

0,75mm²

Distance

12m – xx

Max. 15m

Use shielded cable for the 4 

smaller motor wires.

Use shielded cable for the 3 

smallermotor wires

Max. 30m; Min. 1,5mm²

Gate weight maximum 50% of

maximum motor power rating.

Max. 30m; Min. 1,5mm²

Coax cable (Satellite cable)

50 Ohm

(max. 25m)

Min. 0,75mm²

Max. 30m

Min. 0,75mm²

Max. 20m

Summary of Contents for LYN300 Series

Page 1: ...atické pohony bran modely LYN300 LYN400 série SCS300 Instrucciones Automatismos de puerta automáticos modelos LYN300 LYN400 SCS300 de las series O ËÁ Â ÙfiÌ ÙÔÈ ÌË ÓÈÛÌÔ ÁÎ Ú fi ÔÚÙ ÌÔÓÙ Ï LYN300 LYN400 SCS300 Series Útmutatók SCS300 as sorozatba tartozó LYN300 as és LYN400 as automatikus garázsajtó Upute Automatski pogoni vrata modeli LYN300 LYN400 SCS300 serije Istruzioni Automazioni per cancell...

Page 2: ... 2 0 m 3 0 m 4 0 m 5 0 m 6 0 m 250 kg 180 kg 160 kg 140 kg Wing Weight Wing Size LYN300 LYN300 LYN400 LYN400 0 m 0 5 m 1 0 m 1 5 m 2 0 m 2 5 m 3 0 m 250 kg 180 kg 160 kg Wing Weight Wing Size SCS300 3 5 m 4 0 m ...

Page 3: ...6 DESCRIPTION OF LEDS 6 FUNTIONALITY OVERVIEW OF THE PUSH BUTTONS P1 P2 P3 RESET 6 OPTIONAL ACCESSORIES 7 PHOTOCELLS 8 RADIO AND RADIO PROGRAMMING 8 PROGRAM INTERNET GATEWAY my Q DOOR MONITOR 9 LOOP DETECTOR USAGE 10 DIP SWITCH SETTINGS 11 WING DELAY ADJUSTMENT 11 INITIAL OPERATION BASIC SETTING 12 14 TIMER TO CLOSE AUTO CLOSE 14 FORCE TORQUE OF MOTOR 14 DISPOSAL BATTERY DISPOSAL 14 INDICATION OF ...

Page 4: ...o check with your gate manufacturer for an opener installation reinforcement kit Activate opener only when the gate is in full view free of obstructions Do not allow children to play near the gate Humidity and water destroy the control board Make sure under all circumstances that water humidity or dammed up water cannot penetrate the control board covering Frequently examine the installation for i...

Page 5: ...optional Is mounted on the outside The gate is opened by key or by entering a number 7 Contact strip optional Safeguards the gate on being touched Contact strips can be mounted on the gate or on the pillars If required contact strips must be mounted at a height of up to 2 5m 2 16 en CONTROL BOX The control consists of several components exterior installation box 1 cover for box 1 control 1 transfo...

Page 6: ...s C Fasten transformer on to baseplate using the large screw and large washer D Put the 4 large closure screws through cover of the box Fasten 2 of them left or right approx 2cm into the box After that the cover can be opened to the side E Close box on a trial basis turning the screws all the way in If the lid does not close completely then the box is not fitted to the wall evenly and is therefore ...

Page 7: ...h identical colours distribution box IP65 cable screw joints and fastening material 041ASWG 0482 50 Cable 50m for professional use Consists of 50m of cable 6 pole with identical colours Cut only as much as you need for the current installation General wiring sizes The numbers mentioned in the table below are minimum requirements It is always possible to use larger diameters 230Volt Supply Power to...

Page 8: ...CM475 BROWN GREEN WHITE BROWN GREEN WHITE YELLOW YELLOW RADIO MODULE Model 207399 230 VAC 50 RED RED BLUE BLUE BROWN GREEN WHITE BROWN GREEN WHITE not required not required RED RED BLUE BLUE BROWN GREEN WHITE BROWN GREEN WHITE YELLOW YELLOW ART SUB Closed position Open position external battery ...

Page 9: ...D motor 2 Second opens second red blue To check correct polarity refer to section basic setting and functionality P1 P2 P3 RESET 24V 150mA flashing light accessory Motor1 MASTER BRN brown cable GRN green cable WHT white cable YEL yellow cable Motor2 SECOND BRN brown cable GRN green cable WHT white cable YEL yellow cable Light Contact gate monitor yard lighting PED key switch COM negative pole STOP ...

Page 10: ...ith 829EV door monitor allows optical and acoustical monitoring of the gate position The gate can also be closed with the device BACKUP BATTERY OPTIONAL The terminals serve to reload an externally installed storage battery The integrated recharger is loaded and in case of power failure the battery provides power A new fully charged storage battery may provide power for more than 24 hours Storage b...

Page 11: ... LED flashes photocell disables control board Connection between 1 COM Active when gate is closing reverses gate to open Connection between 2 COM Active when gate is closing and opening Connection between 3 COM Active when gate is opening holds gate in present position until photocell is cleared continues when cleared RADIO AND RADIO PROGRAMMING PROGRAM DELETE REMOTE CONTROLS The receiver has two c...

Page 12: ...the LEDs will blink 3 times and go out 7 The App will tell you if programming was successful and will prompt you to assign a name to the gate PROGRAM DOOR MONITOR Using the RESET Button on the control board 1 Connect power to the door monitor Position the door monitor in a convenient visible place inside the house If this place is too far from the gate opener the connection may not be possible or ...

Page 13: ... truck but do not comply with regulations as single protection since they do not detect people The loop detector control board output is wired as NO signal to the 8 2KOhm safety edge output In case you use safety edges as well Check the functionality you need before installation Interrupt loop DIP OPEN STEP must be on Shadow loop DIP OPEN STEP must be off Other options for loop detectors can be re...

Page 14: ...CS SUB RADIO The DIP RADIO is required to program remote controls For programming procedure please refer to page 8 section radio OFF No programming of remote controls possible ON Programming of remote controls possible Important Switch off DIP RADIO if not in use Wing Delay Adjustment The delay of one wing is required to open and close the wings correctly and to operate the wings with a safe dista...

Page 15: ...anged any time later after completion of the installation Now connect the mains supply 230V to the control board BASIC SETTING 1 Press buttons P1 P2 and P3 simultaneously for approx 2 3 seconds until yellow LED flashes 2 Monitor the gate Press and hold P1 for 1 2 seconds The wing with motor 1 opens If motor 1 closes it is wired incorrectly and the red and blue wires of the motor cable must be rever...

Page 16: ...When the learn LED goes out the programming has finished PROGRAMMING TRAVEL DISTANCES ADVANCED NOTE In this mode P1 must be pressed 9 times With every time the button is pressed a position time is stored This allows programming of SOFT STOP slow travel in order to adjust to application Long or short phases of SOFT STOP are possible 1 Both wings must be closed 2 Press P1 and P2 for approx 5 6 second...

Page 17: ...r changes to the installation rust or inappropriate lubrication it may have to be repaired The control board complies with the latest EU guidelines One of these guidelines specifies that the closing forces at the gate edge must not exceed 400N 40 kg for the last 500 mm before the door is CLOSED Above 500 mm the maximum force at the gate edge must not exceed 1400 N 140 kg If this cannot be ensured a...

Page 18: ...nstallation A Object obstructs safety edge B Defective safety edge C Power too low or broken wire in supply Power supply to control board is too low A Defective supply 230V or malfunctioning contact B Broken wire in supply cable copper cable C The battery accessory to operate the gate whilst power failure is dead EEPROM Fault Power up failed Only LYN SCS Release lever OPEN Defect on relay or major...

Page 19: ... 2 Find and rectify fault s see description of diagnostic LEDs 3 Check photocell connection programming 4 Check terminals and connections 1 Program transmitter 2 Check photocells check diagnostic LEDs 3 DIP RADIO must be off Program travel distance See initial operation diagnosis LED re program travel distance consult dealer specialist 1 Check manual especially 1 2 Motor 2 If motor is moving check...

Reviews: