MAINTENANCE AND STORAGE

Storage

The generator should be started at least once every 14 
days and allowed to run for at least 20 minutes. For 
longer term storage, please follow these guidelines.

Generator Storage

1.  Add a properly formulated fuel stabilizer to the tank.
2.  Be sure all appliances are disconnected from the 

generator.

3.  Run the generator for a few minutes so the treated 

fuel cycles through the fuel system and carburetor.

4.  Turn the fuel valve to the “Off” position.
5.  Let the generator run until fuel starvation has 

stopped the engine. This usually takes a few minutes.

6.  The generator needs to cool acompletely before 

cleaning and storage.

7.  Clean the generator according to the maintenance 

section.

8.  Change the oil.
9.  Remove the spark plug and pour about 1⁄2 ounce 

(14.8 mL) of oil into the cylinder. Crank the engine 
slowly to distribute the oil and lubricate the cylinder.

10. Reattach the spark plug.
11. Store the unit in a clean, dry place out of direct 

sunlight.

Generator Battery

This product is equipped with an automatic battery 
charging circuit. The battery will receive charging 
voltage when the engine is running. The battery will 
maintain a proper charge if the unit is used on a regular 
basis (about once every two weeks). If it is used less 
frequently, the battery should be connected to a trickle 
charger or battery maintainer to keep the battery 
properly charged. If the battery is not able to start the 
engine, it can be started by manually pulling the engine 
recoil cord. If the battery voltage is extremely low, 
the charging circuit may not be able to re-charge the 
battery. In this case, the battery must be connected to a 
standard automotive style battery charger for re-charging 
before it can be used.

Disconnect the Battery

1.  Remove the protective cover from the black/negative 

battery lead.

2.  Disconnect the black/negative lead from the black/

negative terminal on the battery and store the cap 
screw (M5x10) and nut (M5).

3.  Repeat steps 1-2 for the red/positive battery lead.
4.  Store the battery in a cool, dry place.

A Float Charger will maintain the battery condition 
over long storage periods.

NOTE

Charge the Battery

For a generator equipped with batteries for electric 
starting, proper battery maintenance and storage should 
be followed. An automatic battery charger (not included) 
with automatic trickle charging capability should be used 
to charge the battery. Maximum charging rate should not 
exceed 1.5 amps. Follow the instructions included with 
the battery charger. The battery should be fully charged 
at least once per month.

Generator exhaust contains odorless and colorless 
carbon monoxide gas.

To avoid accidental or unintended ignition of your 
remote start generator during periods of storage, 
the following precautions should be followed:

 

– When 

storing the generator for short periods of 

time make sure that the Ignition Switch, the Fuel 
Valve and the Battery Switch are set in the 

OFF 

position. 

 

– When 

storing the generator for extended periods 

of time make sure that the Ignition Switch, the 
Fuel Valve and the Battery Switch are set in the 
the the 

OFF position and the battery leads have 

been 

disconnected from the battery. 

DANGER

Summary of Contents for 71531

Page 1: ...338 0999 www championpowerequipment com 8400 Starting Watts 6750 Rated Watts LPG 9375 Starting Watts 7500 Rated Watts Gas DUAL FUEL GENERATOR SAVE THESE INSTRUCTIONS Important Safety Instructions are...

Page 2: ...r Champion Power Equipment product is designed and rated for continuous operation at ambient temperatures up to 40 C 104 F When your product is needed your product may be operated at temperatures rang...

Page 3: ...ad Generator 15 Capacity 15 Power Management 16 Operation at High Altitude 16 Maintenance and Storage 17 Engine Maintenance 17 Oil 17 Spark Plugs 17 Air Filter 17 Spark Arrester 18 Cleaning 18 Adjustm...

Page 4: ...this information available when ordering parts and when making technical or warranty inquiries Accessories Champion Power Equipment manufactures and sells accessories designed to help you get the most...

Page 5: ...hazardous situation which if not avoided may result in minor or moderate injury CAUTION CAUTION used without the safety alert symbol indicates a potentially hazardous situation which if not avoided m...

Page 6: ...amaged or frayed DO NOT operate generator in wet weather DO NOT allow children or unqualified persons to operate or service the generator Use a ground fault circuit interrupter GFCI in damp areas and...

Page 7: ...generator s running capacity can damage the generator and or electrical devices connected to it DO NOT overload the generator Start the generator and allow the engine to stabilize before connecting el...

Page 8: ...FLAMMABLE AND EXPLOSIVE Fire or explosion can cause severe burns or death Unintentional startup can result in entanglement traumatic amputation or laceration DANGER When adding or removing Gas Turn th...

Page 9: ...l Tank 6 1 gallon 23 L capacity fuel tank 2 Choke Used to start the engine 3 Air Cleaner Protects the engine by filtering dust and debris from the intake air 4 Recoil Starter Used to manually start th...

Page 10: ...al Consult an electrician for local grounding regulations 7 120 Volt AC 30 Amp Twist Lock Receptacle NEMA L5 30R May be used to supply electrical power for the operation of 120 Volt AC 30 Amp single p...

Page 11: ...nge Bolt M10x120 for Wheel 2 Bushing 2 Flat Washer 10 2 Lock Nut M10 2 Support Leg w Vibration Mounts 1 Flange Bolt M8x16 for Support Leg 2 Flange Lock Nut M8 2 Other Oil 1 2 qt 1 1 L LPG Hose With Re...

Page 12: ...lowing tools to install the wheels 17 mm wrench OR adjustable wrench not included Socket wrench with a 16 mm socket not included Pliers not included 1 Before adding fuel and oil tip the generator on i...

Page 13: ...evel in the crankcase falls below the threshold level CAUTION Add Engine Oil DO NOT attempt to crank or start the engine before it has been properly filled with the recommended type and amount of oil...

Page 14: ...an ethanol content of less than 10 by volume 2 DO NOT mix oil with fuel 3 Clean the area around the fuel cap 4 Remove the fuel cap 5 Slowly add fuel to the tank DO NOT OVERFILL Fuel can expand after...

Page 15: ...hat have not been plugged or kept closed must also be purged The purging process should be done by a LPG supplier Cylinders from an exchange supplier should have been purged and filled properly alread...

Page 16: ...when positioning generator Failure to follow proper safety precautions may void manufacturer s warranty Do not operate or store the generator in rain snow or wet weather Using a generator or electrica...

Page 17: ...attery switch to the ON position 7 ELECTRIC START Press and hold the ignition switch to the START position Release as the engine begins to roll over If the engine fails to start within five seconds re...

Page 18: ...ne This usually takes a few minutes 5 Press the engine switch to the OFF position 6 Turn Battery Switch to the Off Position Important Always ensure that the Fuel Valve and the Engine Switch are in the...

Page 19: ...end of the generator near the handle where engine fan air flows out from the generator This air is slightly heated by flowing over the engine The container should not be placed in the path of the muf...

Page 20: ...lug 6 Carefully thread the plug into the engine 7 Use the spark plug tool to firmly install the plug 8 Attach the spark plug wire to the plug For service or parts assistance contact our help line at 1...

Page 21: ...tenance and Storage Federal and local laws and administrative requirements indicate when and where spark arresters are required When ordered spark arresters are required for operation of this generato...

Page 22: ...ulling the engine recoil cord If the battery voltage is extremely low the charging circuit may not be able to re charge the battery In this case the battery must be connected to a standard automotive...

Page 23: ...F6RTC Replacement spark plug NGK BPR6ES or equivalent Make certain the spark plug gap is 0 7 0 8 mm or 0 028 0 031 in An Important Message About Temperature Your Champion Power Equipment product is de...

Page 24: ...56 57 66 23 82 83 84 85 86 87 88 44 65 1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 5 5 16 59 62 63 64 60 61 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 76 89 90 91 92 93 95 97 98 99 94 100 10...

Page 25: ...00800 09 2 Decorative Plate 1 68 152 070031 00 Jacket LPG Hose 3 69 6 5 233 420 2 Frame 1 70 1 6177 1 10 Flange Lock Nut M10 4 Part Number Description Qty 71 152 201200 03 Motor Mount I 2 72 1 6182 10...

Page 26: ...108 85 10 1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 19 20 16 24 25 26 27 28 29 30 31 33 34 35 12 36 30 37 38 23 39 41 42 43 44 46 47 48 49 50 51 52 53 12 54 55 57 58 59 60 61 62 65 66 68 69 70 71 72 7...

Page 27: ...1 56 2 01 010 Stud Bolt M8 35 2 57 2 15 002 F6RTC Spark Plug F6RTC 1 Part Number Description Qty 58 2 08 014 Flange Bolt M10 80 4 59 46 020002 00 Gasket Cylinder Head Cover 1 60 47 021000 00 Cylinder...

Page 28: ...DCW multi purpose meter FUEL CUT SOLENOIL B G B G W G W G G OFF G Y G Y G Y 3 4 5 2 1 6 G Y Charger Br G Y SWITCH lb l la G Y EARTH TERMINAL G Y G Y L14 30R L5 30R 5 20R B W W R R R G Y B B W G Y W W...

Page 29: ...position Generator shuts down during operation Out of fuel Fill the gasoline tank or fill LPG cylinder Low oil level Fill crankcase to the proper level Place generator on a flat level surface Generato...

Page 30: ...nd or labor if this generator is deemed to have been misused neglected involved in an accident abused loaded beyond the generator s limits modified installed improperly or connected incorrectly to any...

Page 31: ...parts and labor For engines less than or equal to 80cc only the fuel tank and fuel line is subject to the evaporative emission control warranty requirements of this section MANUFACTURER S EMISSION CON...

Page 32: ...be warranted for the period of time prior to the first scheduled replacement point for that part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by CP...

Page 33: ...ets Carburetor Purge Port Connector TO OBTAIN WARRANTY SERVICE You must take your CPE engine or the product on which it is installed along with your warranty registration card or other proof of origin...

Reviews: