Overhead Work Procedures
ALL MODELS
All interpretations should take into account the circuit configuration, length,
proximity to other lines; and should be consistent with previous experience
on same circuit with this instrument. If in doubt about interpreting MRVD
reading under any circumstances,
assume circuit is energized and take
appropriate safety precautions.
MRVD INTERPRETATIONS
Reading x Multiplier
Circuit Condition
Approximate line-to-line voltage
Energized
Approximately zero
De-energized
Upscale, but well under line-to-
line voltage
Probably de-energized: reading
due to static.
Do not assume
anything; check circuit condition
by another method.