20016967
5
GB
CORRELATION BETWEEN GAS PRESSURE AND BURNER OUTPUT
To obtain the maximum output, a gas head pressure of 9.3 mbar, relatively to TIGRA 2 CG710 model, is
measured (
M2
, see chapter 3.6, page 7) with the combustion chamber at 0 mbar using gas G20 with a net
heat value of 10 kWh/m
3
(8.570 kcal/m
3
).
3.
INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
3.1
WORKING POSITION
The burner is designed for operation in position
1
only.
Installation in positions
2, 3, 5, 6
and
7
is not recommended as it is likely to hinder the unit’s proper operation
since air damper closure cannot be guaranteed when the burner is on standby.
Installation in position
5
is only possible using the “MULTIBLOC rotation kit”, to be ordered separately.
Installation
4
is prohibited as safety is compromised.
Thermal power
Ga
s pres
sur
e
in
t
h
e
comb
ust
io
n
h
ead
–
mb
ar
D8933
0
50
100
150
200
kW
0
50.000
100.000
150.000
kcal/h
10
8
6
4
2
0
250
200.000
12
911
T
1
91
2T
1
91
3T
1
914
T1
D4450
1
2
3
4
5
6
7