7.4.

 

Alarm Connections 

Alarm Block 1: 

 

Alarm 66 

Block 

Block#-Pair# 

Pin # 

BBU Wire Color 

(per local market) 

Normal 

Contact 

State 

(NC or NO) 

AT&T Alarm 

Label/Verbiage 

Comments or 

Factory/OEM Alarm 

B

B

U

 1

-4

 

1-1 

WHITE/BLUE 

NC 

RBS INTRUSION 

Entry door switch 

contacts 

BLUE/WHITE 

1-2 

WHITE/ORANGE 

NC 

RBS COMMERCIAL 

POWER FAIL 

from PTLC power fail 

relay 

ORANGE/WHITE 

1-3 

WHITE/GREEN 

NC 

RBS PWR AC SPD 

from PTLC surge 

protector 

GREEN/WHITE 

1-4 

WHITE/BROWN 

NC 

RBS SMOKE 

Smoke Detector 

BROWN/WHITE 

B

B

U

 5

-8

 

1-5 

WHITE/SLATE 

NC 

RBS TEMP HIGH 

High temp 

10 

SLATE/WHITE 

1-6 

11 

RED/BLUE 

NC 

RBS TEMP LOW 

Low temp 

12 

BLUE/RED 

1-7 

13 

RED/ORANGE 

NC 

RBS HUMIDITY HIGH 

Humidity Sensor 

14 

ORANGE/RED 

1-8 

15 

RED/GREEN 

NC 

RBS HVAC 1 FAIL 

HVAC Fail 

16 

GREEN/RED 

B

B

U

 9

-12

 

1-9 

17 

RED/BROWN 

NC 

RBS GEN TRANSFER 

SW FAIL 

350A (-48VDC) CB AUX 

contacts 

18 

BROWN/RED 

1-10 

19 

RED/SLATE 

NC 

RBS FIF PDU FUSE 

FAIL 

FIF Fuse Fail 

20 

SLATE/RED 

1-11 

21 

BLACK/BLUE 

  

(SPARE) 

  

22 

BLUE/BLACK 

1-12 

23 

BLACK/ORANGE 

  

(SPARE) 

  

24 

ORANGE/BLACK 

B

B

U

 1

3

-16

 

1-13 

25 

BLACK/GREEN 

NC 

RBS LTE RRU AT DC 

SYS SPD 

Raycap #1 alarm 

26 

GREEN/BLACK 

1-14 

27 

BLACK/BROWN 

NC 

RBS LTE RRU AT DC 

SYS SPD 

Raycap #2 alarm 

28 

BROWN/BLACK 

1-15 

29 

BLACK/SLATE 

NC 

RBS LTE RRU AT DC 

SYS SPD 

Raycap #3 alarm 

30 

SLATE/BLACK 

1-16 

31 

YELLOW/BLUE 

NC 

RBS 5G RRU AT DC 

SYS SPD 

Future (5G) Raycap #1 

Alarm 

32 

BLUE/YELLOW 

 

1-17 

33 

YELLOW/ORANGE 

NC 

RBS 5G RRU AT DC 

SYS SPD 

Future (5G) Raycap #2 

Alarm 

 

34 

ORANGE/YELLOW 

 

1-18 

35 

YELLOW/GREEN 

NC 

RBS 5G RRU AT DC 

SYS SPD 

Future (5G) Raycap #3 

Alarm 

 

36 

GREEN/YELLOW 

 

1-19 

37 

 

 

 

 

 

38 

 

 

1-20 

39 

 

 

 

 

 

40 

 

 

1-21 

41 

 

 

 

 

 

42 

 

 

1-22 

43 

 

 

 

 

 

44 

 

 

1-23 

45 

 

 

 

 

 

46 

 

 

1-24 

47 

 

 

 

 

 

48 

 

 

1-25 

49 

 

 

 

 

 

50 

 

 

NOTE: The Alarm Block configurations shown are standard on all new metal and concrete WICs (Walk-In-Cabinet).  Additional 
alarms should be added as applicable 

 

 

 

Summary of Contents for WIC-101010SXAN1

Page 1: ...13 6 WARRANTY CUSTOMER SERVICE 13 7 SPECIFICATIONS 13 7 1 Regulatory Specifications 13 7 2 Product Specifications 14 7 3 Part Numbers 14 7 4 Alarm Connections 15 1 GENERAL INTRODUCTION 1 1 Document Pu...

Page 2: ...all connect to an interior master ground bar Equipment and power racks are added to the WIC by Worldwide Technologies See their documentation for information about the power equipment included Accesso...

Page 3: ...LT WIC101010 3rd Printing Page 3 of 16 Figure 3 WIC External Components...

Page 4: ...LT WIC101010 Page 4 of 16 3rd Printing Figure 4 WIC Internal Components Front and Right Side Walls Hidden...

Page 5: ...LT WIC101010 3rd Printing Page 5 of 16 Figure 5 WIC with Optional Kits and Equipment Racks Installed Front and Right Side Walls Hidden...

Page 6: ...serious damage s to persons or product Only authorized trained personnel shall install the WIC 3 3 Obtaining Tools and Equipment Obtain the following recommended or needed items for installing the WIC...

Page 7: ...ng to local practices including safety helmets and steel toed shoes Do not operate thehoisting equipment until all stabilizer are extended and in firm contact with the ground or adequate support struc...

Page 8: ...t the helical upright allowing it to swing free of the ground 5 Maneuver the helical directly over the installation point 6 Lower the helical until the point of the helical is forced into the ground o...

Page 9: ...ling hardware between the frame and the nine footers Be sure to maintain 18 inches from grade to the top of the frame which is the bottom of the WIC Start by leveling the four corners first then adjus...

Page 10: ...0 10 32 26 10 12 24 50 10 1 4 20 M6 60 5 5 5 5 16 18 125 5 10 4 5 3 8 16 180 5 15 0 5 1 2 13 500 2 41 7 2 5 8 11 1000 1 83 3 1 Use these values for the Grade 8 mounting hardware Thread Size Ft lbs Coa...

Page 11: ...LT WIC101010 3rd Printing Page 11 of 16 Figure 11 Electrical Diagram...

Page 12: ...this timer so that fresh air will be drawn into the WIC while work is being performed Second the IVS can be activated by an internal temperature probe connected to the controller that turns the fans o...

Page 13: ...the GFCI duplex receptacle periodically to ensure it is working The unit meets UL 943 which requires an auto monitoring self testing feature A flashing or solid red LED indicates a fault If the unit c...

Page 14: ...97 WIC10KHVACKT kit Dantherm 708349 48VDC Cooling Capacity 10000BTU Environmental Operating Temp Range Outside Enclosure 40 to 115 F 40 to 46 C Operating Temp Range Inside Enclosure 40 to 131 F 40 to...

Page 15: ...12 1 9 17 RED BROWN NC RBS GEN TRANSFER SW FAIL 350A 48VDC CB AUX contacts 18 BROWN RED 1 10 19 RED SLATE NC RBS FIF PDU FUSE FAIL FIF Fuse Fail 20 SLATE RED 1 11 21 BLACK BLUE SPARE 22 BLUE BLACK 1 1...

Page 16: ...RFA MULT 14 ORANGE RED 2 8 15 RED GREEN NC RBS BATT TEMP HIGH DC PLANT HITEMP1 16 GREEN RED BBU 25 28 2 9 17 RED BROWN SPARE 18 BROWN RED 2 10 19 RED SLATE SPARE 20 SLATE RED 2 11 21 BLACK BLUE SPARE...

Reviews: