Product Specifications 

Physical

 

Dimensions and Weight 

10

”Hx10”Wx10”D,  

Approx. 7850 lbs. without equipment racks 
Approx. 13,850 lbs. with equipment racks 

Materials 

Steel 

Color 

Exterior: Cool white; interior floor: light gray 

Electrical 

Ventilation System 

Charles IVS, 83-008367-0, -48VDC 

Bonding and Grounding 

12 and 24 position ground bars on the sides and rear (external) 
46 position master ground bar on rear wall (internal) 
1 pair of ground studs on the rear for earth ground 

Cable Entry 

See Figure 2 and section 3.7.7 

Thermal 

6000W CTMS 

Charles Industries 99-004920-0 

Cooling Capacity at Full Speed 

320 W/K 

Heat Removal 

ΔT (max. internal – ambient) 

Capacity 

19⁰C 

6000W 

10⁰C 

3200W 

5⁰C 

1600W 

 

Heating Capacity 

500W below 15⁰C / 1000W below 10⁰C 

CTMS Operating Temperature for Cooling 

77⁰F to 95⁰F 

CTMS Operating Temperature for Heating 

50⁰F to 41⁰F 

Average Shelter Temperature 

90⁰F to 95⁰F 

HVAC (only if using the 97-WIC10KHVACKT kit) 

Dantherm 708349, -48VDC 

Cooling Capacity 

10000BTU 

Environmental 

Operating Temp. Range, Outside Enclosure 

-40° to +115°F,  -40° to 46°C 

Operating Temp Range, Inside Enclosure 

-40° to +131°F,  -40° to 55°C 

Humidity 

0 to 95% (non-condensing) 

Altitude 

Up to 2,000 meters (6560 feet) 

Kits and Replacement Parts 

Touch-up Paint 

Exterior: 02-000634-0; interior floor: 02-000736-0 

4-Wire Door Alarm Switch (Black) 

17-400319-0 

External Stair Kit 

97-1010WICSTRKIT; CEQ.46634 

Microwave Port Kit 

97-MICWVPRTKIT; CEQ.46671 

DC Generator Port Kit 

97-DCGENPORTKIT; CEQ.46636 

Cable Entry Port Kit 

97-9CBLPORKIT; CEQ.46663 

HVAC Kit 

97-WIC10KHVACKT 

Exterior Light 

99-005035-0 

Helical Mounting Kit 

EMI part number: 1000-0000-0101 
AT&T part number: 

CEQ.19785

 

Gravity Mounting Kit 

EMI part number: 1000-0000-0162 
AT&T part number: 

CEQ.46388

 

Extension Mounting Kit 

EMI part number: D1007-0000-0012 
AT&T part number: CEQ.20061 

Table 1 

WIC Specifications 

 

7.3.

 

Part Numbers 

Charles Part Number 

Description 

NESC ID 

WIC-101010SXAN1 

NSB 10x10 Walk-in-Cabinet (WIC) Fully Configured Ericsson RAN 

ERNSB10x10WIC-01 

NSB 10x10 Walk-in-Cabinet (WIC) Fully Configured Nokia RAN 

NONSB10x10WIC-01 

 

 

 

Summary of Contents for WIC-101010SXAN1

Page 1: ...13 6 WARRANTY CUSTOMER SERVICE 13 7 SPECIFICATIONS 13 7 1 Regulatory Specifications 13 7 2 Product Specifications 14 7 3 Part Numbers 14 7 4 Alarm Connections 15 1 GENERAL INTRODUCTION 1 1 Document Pu...

Page 2: ...all connect to an interior master ground bar Equipment and power racks are added to the WIC by Worldwide Technologies See their documentation for information about the power equipment included Accesso...

Page 3: ...LT WIC101010 3rd Printing Page 3 of 16 Figure 3 WIC External Components...

Page 4: ...LT WIC101010 Page 4 of 16 3rd Printing Figure 4 WIC Internal Components Front and Right Side Walls Hidden...

Page 5: ...LT WIC101010 3rd Printing Page 5 of 16 Figure 5 WIC with Optional Kits and Equipment Racks Installed Front and Right Side Walls Hidden...

Page 6: ...serious damage s to persons or product Only authorized trained personnel shall install the WIC 3 3 Obtaining Tools and Equipment Obtain the following recommended or needed items for installing the WIC...

Page 7: ...ng to local practices including safety helmets and steel toed shoes Do not operate thehoisting equipment until all stabilizer are extended and in firm contact with the ground or adequate support struc...

Page 8: ...t the helical upright allowing it to swing free of the ground 5 Maneuver the helical directly over the installation point 6 Lower the helical until the point of the helical is forced into the ground o...

Page 9: ...ling hardware between the frame and the nine footers Be sure to maintain 18 inches from grade to the top of the frame which is the bottom of the WIC Start by leveling the four corners first then adjus...

Page 10: ...0 10 32 26 10 12 24 50 10 1 4 20 M6 60 5 5 5 5 16 18 125 5 10 4 5 3 8 16 180 5 15 0 5 1 2 13 500 2 41 7 2 5 8 11 1000 1 83 3 1 Use these values for the Grade 8 mounting hardware Thread Size Ft lbs Coa...

Page 11: ...LT WIC101010 3rd Printing Page 11 of 16 Figure 11 Electrical Diagram...

Page 12: ...this timer so that fresh air will be drawn into the WIC while work is being performed Second the IVS can be activated by an internal temperature probe connected to the controller that turns the fans o...

Page 13: ...the GFCI duplex receptacle periodically to ensure it is working The unit meets UL 943 which requires an auto monitoring self testing feature A flashing or solid red LED indicates a fault If the unit c...

Page 14: ...97 WIC10KHVACKT kit Dantherm 708349 48VDC Cooling Capacity 10000BTU Environmental Operating Temp Range Outside Enclosure 40 to 115 F 40 to 46 C Operating Temp Range Inside Enclosure 40 to 131 F 40 to...

Page 15: ...12 1 9 17 RED BROWN NC RBS GEN TRANSFER SW FAIL 350A 48VDC CB AUX contacts 18 BROWN RED 1 10 19 RED SLATE NC RBS FIF PDU FUSE FAIL FIF Fuse Fail 20 SLATE RED 1 11 21 BLACK BLUE SPARE 22 BLUE BLACK 1 1...

Page 16: ...RFA MULT 14 ORANGE RED 2 8 15 RED GREEN NC RBS BATT TEMP HIGH DC PLANT HITEMP1 16 GREEN RED BBU 25 28 2 9 17 RED BROWN SPARE 18 BROWN RED 2 10 19 RED SLATE SPARE 20 SLATE RED 2 11 21 BLACK BLUE SPARE...