The cable system consists of retro fitting plug sockets which offers the following options. (Please see figure 5).
The battery manual override option is a back supply in case of a power failure / power cut to the property. The
battery holder and adaptor lead are provide as an optional extra. It is good practice to demonstrate the battery
option to the customer during the commissioning process.
CHECKING GAS SOUNDNESS
Checking gas soundness and running pressure.
Turn on the supply to the appliance and check for tightness in accordance with the current codes of practice.
Turn off the gas supply at the external isolation valve.
Remove the pressure test point screw from the inlet elbow and connect the pressure gauge.
Turn on the gas to the appliance at the isolation valve.
Light the appliance as described in the user instruction section 2. Operating the appliance.
Check the inlet pressure is 20 mbar +/- 1.0 mbar for natural gas or 37 mbar +/-1.0 mbar for LPG with other
appliances running.
Turn off gas supply, at the isolation valve. Disconnect the pressure gauge and replace the pressure test point screw.
Turn on the appliance and check the pressure test point for tightness with detection fluid.