Once fuel bed is fitted refit the glass
Locate the glass panel within the bottom retaining slot and push back against the
seals. (Please see Fig 11).
Position the top fixing bracket over the top edge of the glass panel and slide over
the four M4 studs.
Using the four M4 nuts previously removed. Tighten the top glass fixing using
the nut runner provided with the appliance.
CHECKING FOR COMBUSTION PRODUCTS CLEARENCE
Spillage Test Procedure.
(Please note this test should be taken with the decorative door fully open)
Light the appliance on maximum setting.
Close all the doors and windows.
After five minutes fit the smoke match within match holder and position as illustrated in Figure 13 with the head of
the match just inside the inlet air channel.
Run the match along the edge of the inlet air channel. All smoke must be drawn into the inlet channel if the spillage
test is satisfactory.
If spillage occurs wait a further five minutes and repeat the test.
Repeat the test with doors open and with any extractor fans in other rooms in operation.
If spillage is detected the cause must be discovered and the fault corrected. If the fault cannot be corrected.
Disconnect the fire from the gas supply and seek expert advice. Spillage can be caused by a restriction in the flue
system, down draught or insufficient ventilation into the room where the fire is installed.