Table 1- Installer’s Menu
#
Mnemonic
Limits
Factory Preset
Meaning
1
0 … 150
50
Determines the rotation speed on Manual and
Standby modes.
2
000 … 001
001
Buzzer activation option. When 000 buzzer
remains silent.
3
tL
°C … 150°C
100°C
Determines the maximum temperature limit for
which proportional speed control is performed. For
greater temperatures blower is fully on.
4
20°C
...
tH
°C
50°C
Determines the minimum temperature limit for
which proportional speed control is performed. For
lower temperatures blower is totally inactive.
5
rL
… 150
150
Maximum rotation blower speed
6
20 …
rH
40
Minimum rotation blower speed (*)
7
70°C ... 30°C
55°C
Temperature in which in Standby mode the blower
is activated.
8
1°C … 30°C
5°C
Temperature deactivation hysteresis in Standby
mode.
9
50°C … 200°C
180°C
Alarm temperature in which audible signal is
activated.
10
100°C … 250°C
200°C
Maximum temperature detection limit. Regardless
of the selected operation mode device activates
blower on maximum speed when this limit
exceeded.
Exit from installer’s menu