HEALTH & SAFET Y PRECAUTIONS
This is particularly necessary if the room is
double glazed. It must be positioned such that it is not liable to
blockage.
In addition to these instructions the requirements of BS.8303 and
BS EN 15287-1:2007 must be fulfilled. Local Authority Bylaws and
Building Regulations regarding the installation of Solid Fuel burning
appliances, flues and chimneys must also be observed, including those
referring to national and European Standards.
SPECIFICATION
Please take care when installing the stove that the requirements of
the Health and Safety at Work Act 1974 are met.
Some types of fire cement are caustic and should not be allowed to
come into contact with the skin. In case of contact wash with plenty
of water.
If there is a possibility of disturbing any asbestos in the course of
installation then please use appropriate protective equipment.
There must not be an extractor fan fitted in the same room as the
stove as this can cause the appliance to emit fumes into the room.
There must be an adequate air supply into the room in which the
appliance is installed to provide combustion air. The combustion air
supply must be via a permanently open vent. The minimum free area
is 62.7cm (9.7 in ) .
2
2
CHIMNEY
HEARTH AND FIRE SURROUND
The stove must stand on a fireproof hearth and must be situated at
least the following distances from any combustible material:-
In order for the appliance to perform satisfactorily the chimney height
must not be less than 4 metres measured vertically from the outlet of
the stove to the top of the chimney. The minimum internal chimney
size is
This stove is
to be used in a shared flue. If an existing chimney is
to be used it must be swept and checked, it must be in good
condition, free from cracks and blockages, and should not have an
excessive cross sectional area. If you find that the chimney is in poor
condition then expert advice should be sought regarding the necessity
of having the chimney lined. If it is found necessary to line the
chimney then a lining suitable for Solid Fuel must be used.
If there is no existing chimney then a prefabricated block chimney or
a twin walled insulated stainless steel flue to with BS EN 15287-1:
2007 can be used either internally or externally. These chimneys
must be fitted in accordance with the manufacturers instructions and
Building Regulations.
Anki pumice liners or chimney blocks will give a highly insulated
chimney which will work well with all fuels. For details ring Anki
Chimney Systems on (01983) 527997.
Single wall flue pipe is suitable for connecting the stove to the
chimney but is not suitable for using for the complete chimney.
If it is found that there is excessive draw in the chimney then a
draught stabiliser should be fitted.
It is important that there is sufficient draw in the chimney and that
the chimney does not suffer from down-draught. When the chimney
is warm the draw should be not less than 0.1 inches water gauge. If in
doubt about the chimney seek expert advice.
The hearth must be at least 12mm (0.5inches) thick. The positioning
of the stove and the size of the hearth are governed by building
regulations for Class 1 appliances. These building regulations state
that the hearth must extend in front of the stove by at least 300mm
(12 inches) and to the sides of the stove by at least 150mm (6
inches). When the fire door is open, it extends beyond the front of
the stove by 414mm (16.3in).
150mm diameter (6 inches) or 150mm x 150mm.
NOT
Side
100mm (4in)
Back
100mm (4in)
The outputs were obtained burning:
1) seasoned hardwood over a 1.5 hourly re-fuelling cycle.
2) Welsh Anthracite over a 4 hourly re-fuelling cycle.
®
charnwood
INSTALLATION INSTRUCTIONS
Specification
Nominal Heat Output (kw)
Space Heating Output (kw)
Water Heating Output (kw)
Normal Flue Gas Temp. (
Flue GasMass Flow g/s
Max Water Pressure Bar (ft.
°C)
H O)
Min Distance from combustibles
and also for access:
Sides (mm)
Back (mm)
Max Hearth Temp.(°C)
Min Flue Draught Pa (in water)
Boiler Capacity Litres
Weight (kg):
Low stand
Store Stand
Centre Stand
2
11
4.6
7.1
6.4
9.3
315 353
8.6 11.6
1.5 (50)
100
100
53
25 (0.1)
8.4
127
133
146
(15,696 Btu/h)
(24,226 Btu/h)
(21,838 Btu/h)
(31,733 Btu/h)
(37,533 Btu/h) 16.4 (55,960 Btu/h)
Wood Anthracite
10
Summary of Contents for Cove 2B
Page 1: ... Operating Installation Instructions charnwood ...
Page 2: ......