Fig.9. Vertical register plate with bricked up fireplace
Fig. 10. Horizontal register plate with rear flue connection
of pump failure. All pipework in the primary circuit must be 28 mm
diameter and the gravity flow pipe must rise continuously from the
boiler to the open vent. Two typical systems are shown in Figures 6
and 7
If the appliance is used to heat a small central heating system then the
heat output to the room from the fire will be reduced.
Fitting a radiator in the same room as the fire is recommended as it
will allow greater flexibility in the way that the system is operated as
well as ensuring that there is sufficient heat.
Connect the heating system to the boiler ensuring that the primary
flow pipe rises continuously from the appliance to the vent. Fill the
system with water and check for leaks.
The circulating pump may be controlled by means of time switches,
room thermostats or outdoor thermostats. Radiators may be either
manually or thermostatically controlled. These controls will all work
in conjunction with the thermostat on the appliance and the low limit
pipe thermostat.
We recommend fitting a pipe thermostat onto the gravity return to
act as a low limit thermostat This should be wired into the mains
supply to the pump so that if the gravity return temperature drops
below 45º C then the pump will cut out. This will help to prevent
condensation forming on the boiler faces and will thereby increase
the life of the boiler. It will also ensure that priority is given to the
domestic hot water. These thermostats are available from
Charnwood if you are unable to obtain them locally.
If the vertical rear flue connector (shown in Fig.12) is used then the
chimney may be swept through the appliance.
Horizontal lengths of flue must be kept to a minimum and should not
be more than 150mm (6 inches) long. The sealing face of the flue
collar should be coated with fire cement before fixing to the body of
the stove using the two screws provided. The blanking plate must be
removed, sealed with fire cement and refitted, care being taken to
ensure that the fold on the clamping plate is in line with the lugs on
the firebox as shown on the label on the clamping plate. Ensure that
the clamping plate does not prevent the throat plate from seating
correctly. All flue connections must be well sealed.
SYSTEM CONTROLS
CONNECTIONS TO FLUES
There are several ways of connecting the stove to the flue. These are
illustrated in figures9 to 12
SOOT DOORS
UNPACKING THE STOVE
It is possible to pass a 16 inch diameter sweeps brush through the
appliance but in most back outlet installations it will be necessary to
have a soot door to enable the chimney to be swept. This may either
be in the actual brickwork of the chimney or in the register plate.
Various types and positions of soot doors are shown in figures 9 to
12.
The stove arrives bolted and shrink-wrapped to its pallet. The
wrapping is first removed, then the stove released from the pallet by
removing the 4 pallet bolts using a 10mm spanner. The pallet brackets
can now be removed from the stove by tilting it and using a 13mm
spanner to remove the bolts. These 4 bolts are required for levelling
on the Low Stand or fixing on the Centre Stand, but are not used on
the Store Stand. The Stove comes with the Low Stand fitted and if
this is to be used, the Stove may now be moved to its final position.
Alternative Soot Door Positions
Register Plate
With Soot Door
Register Plate
Soot Door
in side or rear
of Chimney
®
charnwood
INSTALLATION INSTRUCTIONS
12
Summary of Contents for Cove 2B
Page 1: ... Operating Installation Instructions charnwood ...
Page 2: ......