61
MiniFlex
®
MA193
Nominal Range
100 / 400 / 2,000 Aac
Measurement Range
50 mA to 2400 A
ac
Maximum Clamping Diameter
Length = 250 mm; Ø = 70 mm
Length = 350 mm; Ø = 100 mm
Variation of the position of the
conductor in the sensor
≤
2,5%
Adjacent conductor carrying
alternating current
> 40 dB typical at 50/60 Hz for a conductor touching the sensor and
> 33 dB near the snap
Safety
IEC 61010-2-032, Pollution degree 2, 600 V CAT IV, 1000 V CAT III
Table 13
Note:
Currents < 0.05% of the nominal range will be set to zero.
The
nominal ranges are reduced to 50/200/1000 A
ac
at 400 Hz.
MiniFlex
®
MA194
Nominal Range
100 / 400 / 2,000 / 10,000 Aac (for the 1000 mm model)
Measurement Range
50 mA to 2400 A
ac
Maximum Clamping Diameter
Length = 250 mm; Ø = 70 mm
Length = 350 mm; Ø = 100 mm
Length = 1000 mm; Ø = 320 mm
Variation of the position of the
conductor in the sensor
≤
2,5%
Adjacent conductor carrying
alternating current
> 40 dB typical at 50/60 Hz for a conductor touching the sensor and
> 33 dB near the snap
Safety
IEC 61010-2-032, Pollution degree 2, 600 V CAT IV, 1000 V CAT III
Table 14
Note:
Currents < 0.05% of the nominal range will be set to zero.
The
nominal ranges are reduced to 50/200/1000/5000 A
ac
at 400 Hz.
b) PAC93 clamp
Note:
Power calculations are zeroed when the current is zeroed.
PAC93 clamp
Nominal Range
1000 A
ac
, 1400 A
dc
max
93
Measurement Range
1 to 1000 A
ac
, 1 to 1300 A
peak ac+dc
Maximum Clamping Diameter
One 42 mm or two 25.4 mm conductors or two 50 x 5 mm bus bars
Variation of the position of the
conductor in the clamp
< 0,5%, DC to 440 Hz
Adjacent conductor carrying
alternating current
> 40 dB at 50/60Hz
Safety
IEC 61010-2-032, Pollution degree 2, 300 V CAT IV, 600 V CAT III
Table 15
Note:
Currents < 1 A
ac
/
dc
will be set to zero in AC distribution systems.
Summary of Contents for pel 102
Page 1: ...Power energy logger EN User s manual PEL 102 PEL 103 PEL 104 ...
Page 24: ...24 Aggregation period Date and time IP address scrolling Wi Fi address scrolling PEL104 ...
Page 36: ...36 Three phase 3 wire balanced 3P 3W b U12 U23 U31 f P Q S PF P Q S tan ϕ I1 I2 I3 ϕ I1 U12 ...
Page 38: ...38 Three phase 4 wire wye balanced 3P 4WYb I1 I2 I3 V1 V2 V3 VN U12 U23 U31 f P Q S tan ϕ ...