11
The bottom and top strips provide the following indications:
Icon
Description
Indicator of a reversal of phase order or a missing phase (displayed for three-phase distribution networks, and
only in measurement mode; see the explanation below)
Data available for recording.
Indication of the power quadrant.
Measurement mode (instantaneous values). See § 4.4.1.
Power and energy mode. See § 4.4.2.
Configuration mode. See § 3.5.
Table 3
Phase order
The phase order icon is displayed only when the measurement mode is selected.
The phase order is determined every second. If it is not correct, the
symbol is displayed.
The phase order for the voltage inputs is displayed only when the voltages are displayed.
The phase order for the current inputs is displayed only when the currents are displayed.
The phase order for the voltage and current inputs is displayed only when the powers are displayed.
The source and load must be parameterized using PEL Transfer to define the direction of the energy (imported or exported).
2.7. INDICATORS
Indicators
Colour and function
Green indicator: Mains
Indicator lit: the instrument is connected to mains via the external power supply (optional mains power unit).
Indicator off: the instrument is powered by the battery.
Orang/red indicator: Battery
Indicator off: battery fully charged.
Orange indicator lit: battery charging.
Indicator orange and blinking: battery is recovering from a full discharge.
Indicator red and blinking: battery low (and no mains power).
Red indicator: Phase order
Indicator off: phase rotation order correct.
Indicator blinking: phase rotation order incorrect, i.e., one of the following cases:
the phase difference between the phase currents is 30° greater than normal (120° in three-phase
and 180° in two-phase).
the phase difference between the phase voltages is 10° greater than normal.
the phase difference between the currents and voltages of each phase is greater than 60° with
respect to 0° (on a load) or 180° (on a source).
OL
Red indicator: Overshoot of the measurement range
Indicator off: no overshoot on the inputs.
Indicator blinking: overshoot on at least one input, a lead is missing or connected to the wrong terminal.
Summary of Contents for PEL 106
Page 1: ...Power energy logger EN User s manual PEL 106 ...
Page 34: ...34 Three phase 3 wire balanced 3P 3W b U12 U23 U31 f P Q S PF P Q S tan ϕ ϕ I1 U12 I1 I2 I3 ...
Page 36: ...36 Three phase 4 wire wye balanced 3P 4WYb I1 I2 I3 V1 V2 V3 VN U12 U23 U31 f P Q S tan ϕ ...
Page 37: ...37 DC 2 wire dC 2W DC 3 wire dC 3W P Q S PF ϕ I1 V1 P Q S tan ϕ P I V VN I1 I2 IN ...
Page 38: ...38 DC 4 wire dC 4W P I1 I2 I3 IN V1 V2 V3 VN V1 V2 VN ...
Page 46: ...46 Two phase 3 wire 1P 3W I1 I2 V1 V2 U12 VN P Q S P Q S ...
Page 49: ...49 P Q S ...