2.0 C-Linx PROGRAMMING OPTIONS
2-2
Cheetah Xi Programming Manual
Rev 1, 09/2013
P/N: 06-651
2.2
SOFTWARE PROGRAMMING FEATURES
The following tables identify the configurable features that can be changed by using the panel’s programming
software C-Linx. The table also identifies features that are available, but not permitted to be used per the
Cheetah Xi system’s UL listing.
Exhibit 2-1: Programming Features
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for
Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Main Board Configuration Options
MISC.
Miscellaneous Options
AC Trouble Delay
Y
0-30 hours, (
Default 2)
1–3
Abort Type
N
1 – 6
(Default 2)
1-4
Fan Restart
Y
Automatic
/Manual
Drill/Silence/Acknowledge N
Enabled
/ Disabled
Enabled 1,2
Auto Message
Y
Enabled /
Disabled
Walktest Y
Enabled
/ Disabled
Supervision Options
Transformer Y
120VAC
/ 240VAC
Loop Style (SLC)
Y
4
,6, or 7 (A, B, or X)
Ground Fault Level 1
N
Enabled
/ Disabled
Enabled 2
Ground Fault Level 2
N
Enabled /
Disabled
Enabled 2,
3
Main Battery
N
Supervised
/ Unsupervised
Super.
Auxiliary Battery
N
Supervised /
Unsupervised
Super.
Auxiliary Loop Module Present
Y
Enabled /
Disabled
Auxiliary Power Module Present
Y
Enabled /
Disabled
Eclipse Device Error Trouble
Y
Enabled
/ Disabled
Yes 4
AHU Fire Dept Key Required for
AHU Restart
Y
Yes /
No
Battery Cutoff
Y
Loop # and Address #
(L: 1-4 Address: 0-254)
Silence Options
Unsilence Time
Y
1-
24
hours
Silence Reminder
Y
Enabled /
Disabled
Silence Inhibit
Y
Enabled /
Disabled
Positive Alarm Sequence
Y
Enabled /
Disabled
Silence Mode
Y
UL
5
Notes:
1.
City of Chicago does not allow use of Drill, Silence and Acknowledge switches.
2.
Can only be changed with Factory Level password. Level 2 required for use with solenoids
3.
Level 2 ground fault detection required for use with solenoids.
4.
If device on SLC has an internal error then the panel produces a trouble state (Enabled) and does not just logs it (Disabled).
(i.e. Checksum Error)
5.
An audible signal that has been silenced at the protected premises shall automatically resound and remain energized until
silenced and retransmitted the signal to any supervising station to which the original signal was transmitted, as applicable, at
least once every 24 hours until the condition is corrected and the product is restored to the normal supervisory condition.