background image

2.0  C-Linx PROGRAMMING OPTIONS

 

 

2-2 

Cheetah Xi Programming Manual 

 

Rev 1, 09/2013 

P/N: 06-651 

 

2.2 

SOFTWARE PROGRAMMING FEATURES 

The following tables identify the configurable features that can be changed by using the panel’s programming 
software C-Linx.  The table also identifies features that are available, but not permitted to be used per the 
Cheetah Xi system’s UL listing. 

Exhibit 2-1:  Programming Features 

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES 

This product incorporates field-programmable software.  In order for the product to comply with the requirements in the Standard for Control Units and Accessories for 

Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below. 

Circuit or 

Component 

Program Feature or Option 

Permitted 

in UL 

864? 

(Y/N) 

Possible Settings 

(Defaults shown bold) 

Settings 

permitted 

in UL 864 

Notes 

Main Board Configuration Options 

MISC. 

Miscellaneous Options 

AC Trouble Delay 

0-30 hours, (

Default 2)

 

1–3  

Abort Type 

1 – 6

 (Default 2) 

1-4  

Fan Restart 

Automatic

/Manual 

 

 

Drill/Silence/Acknowledge N 

Enabled 

/ Disabled

 

Enabled 1,2 

Auto Message 

Enabled / 

Disabled 

 

 

Walktest Y 

Enabled 

/ Disabled 

 

 

Supervision Options 

Transformer Y 

120VAC 

/ 240VAC 

 

 

Loop Style (SLC) 

4

,6, or 7 (A, B, or X) 

 

 

Ground Fault Level 1 

Enabled 

/ Disabled

 

Enabled 2 

Ground Fault Level 2 

Enabled / 

Disabled 

Enabled 2, 

Main Battery 

Supervised 

/ Unsupervised 

Super.  

Auxiliary Battery 

Supervised / 

Unsupervised

 

Super.  

Auxiliary Loop Module Present 

Enabled / 

Disabled

 

 

 

Auxiliary Power Module Present 

Enabled / 

Disabled

 

 

 

Eclipse Device Error Trouble 

Enabled

 / Disabled 

Yes 4 

AHU Fire Dept Key Required for 
AHU Restart 

Yes / 

No

 

 

 

Battery Cutoff 

Loop # and Address # 
(L: 1-4  Address: 0-254) 

 

 

Silence Options 

Unsilence Time 

1-

24

 hours 

 

 

Silence Reminder 

Enabled / 

Disabled

 

 

 

Silence Inhibit 

Enabled / 

Disabled

 

 

 

Positive Alarm Sequence 

Enabled / 

Disabled

 

 

 

Silence Mode 

UL   

 5 

Notes: 

1. 

City of Chicago does not allow use of Drill, Silence and Acknowledge switches. 

2. 

Can only be changed with Factory Level password.  Level 2 required for use with solenoids 

3. 

Level 2 ground fault detection required for use with solenoids. 

4. 

If device on SLC has an internal error then the panel produces a trouble state (Enabled) and does not just logs it (Disabled).  
(i.e. Checksum Error) 

5. 

An audible signal that has been silenced at the protected premises shall automatically resound and remain energized until 
silenced and retransmitted the signal to any supervising station to which the original signal was transmitted, as applicable, at 
least once every 24 hours until the condition is corrected and the product is restored to the normal supervisory condition.   

Summary of Contents for 10-068

Page 1: ...Programming Manual P N 06 651 Rev 1 September 2013 10 068 Cheetah Xi Addressable Fire Suppression Control System ...

Page 2: ...ty returns must be returned from an authorized Fike Distributor Contact Fike s Marketing department for further warranty information Fike maintains a repair department that is available to repair and return existing electronic components or exchange purchase previously repaired inventory component advance replacement All returns must be approved prior to return A Material Return Authorization MRA ...

Page 3: ...es Using C Linx Device Address Function 3 13 4 0 Configuration Menu 4 1 4 1 Configuration Menu 4 1 4 2 Configuration Menu 1 4 1 4 2 1 How to Configure a Field Device 4 1 4 2 1 1 How to Change a Devices Alarm Features 4 2 A How to Modify a Sensor 4 3 B How to Modify a Control or Relay Module 4 3 C How to Modify a Monitor Module 4 7 D How to Modify a Pull Station 4 8 E How to Delete a Device from th...

Page 4: ...Release Features 4 36 4 5 2 5 How to Select VESDA Communication Command Set 4 7 4 5 3 How to Configure Auxiliary Power Circuits as AUX NACs 4 7 4 5 3 1 How to Set an Auxiliary Power Circuit as an AUX NAC 4 38 4 5 3 2 How to Assign Zones to the AUX NAC Circuit 4 39 4 5 4 How to Assign Power Cut Off Relay Address 4 40 4 5 5 How to Configure Panel Relays and Optional Modules 4 40 4 5 5 1 How to Set O...

Page 5: ... 4 3 Alarm Features Screen 4 2 4 4 Alarm Features Screen Sensors and Detectors 4 3 4 5 Alarm Features Screen Control Module 4 3 4 6 Any of 3 Zones Function Screen 4 4 4 7 All of 3 Zones Function Screen 4 5 4 8 Select Device Function Screen 4 6 4 9 Row Anding Function Screen 4 6 4 10 Alarm Features Screen Monitor Module 4 7 4 11 Alarm Features Screen Pull Station Module 4 8 4 12 Delete Device Scree...

Page 6: ...d Set Screen 4 37 4 59 AUX NAC Menu 4 37 4 60 AUX NAC Functions Screen 4 38 4 61 AUX NAC Functions Screen 4 38 4 62 AUX NAC Zone Assignment Screen 4 39 4 63 Power Cut Relay Assignment Screen 4 40 4 64 Relay Configuration Menu 4 40 4 65 Select Module Screen 4 41 4 66 Relay Functions Screen 4 42 4 67 Relay Zone Assign Screen 4 43 4 68 Fan Restart Configuration Screen 4 44 4 69 Configuration Menu 5 4...

Page 7: ...he system If you can not locate the distributor please call Fike Customer Service for locating your nearest distributor or go to our web site at www fike com If you are unable to contact your installing distributor or you simply do not know who installed the system you can contact Fike Fire Alarm Product Support at 888 628 FIKE 3453 Option 2 Monday through Friday 8 00 AM to 4 30 PM CST 1 3 SAFETY ...

Page 8: ...ent Title Part Number Cheetah Xi Addressable Fire Suppression Control System Installation Manual 06 356 Cheetah Xi Addressable Fire Suppression Control System Operation Maintenance Manual 06 356 2 1 5 REVISION HISTORY Document Title Cheetah Xi Addressable Fire Suppression System Programming Manual Document Reorder Number 06 651 Revision Section Date Reason for Change 0 All Sections 04 2012 Separat...

Page 9: ...cription of the configuration parameters that can changed at the panel To set all operating parameters for the system you must use the panel s PC programming software C Linx Section 2 2 provides a complete listing of the programming features that are available through C Linx for your reference Refer to Fike document 06 448 C Linx Configuration Software for software details It is important to keep ...

Page 10: ...former Y 120VAC 240VAC Loop Style SLC Y 4 6 or 7 A B or X Ground Fault Level 1 N Enabled Disabled Enabled 2 Ground Fault Level 2 N Enabled Disabled Enabled 2 3 Main Battery N Supervised Unsupervised Super Auxiliary Battery N Supervised Unsupervised Super Auxiliary Loop Module Present Y Enabled Disabled Auxiliary Power Module Present Y Enabled Disabled Eclipse Device Error Trouble Y Enabled Disable...

Page 11: ...le Y Silenceable Non silenceable Zone Assignment Y 1 254 Circuit Y Enabled Disabled Drill Y Enabled Disabled Walktest Y Enabled Disabled Non Silence for Waterflow Activation Y Enabled Disabled Panel Sync Protocol Y Gentex System Sensor Wheelock Relays P2 Main Board Relay Relay Selection Y R1 R2 4 State Activation Y Alarm Pre Alarm 1 Pre Alarm 2 Supervisory Trouble Process Zone Disable Release Pre ...

Page 12: ...ble Y Non Silenceable Silenceable Zone Assignment Y 1 254 Relay Y Enabled Disabled Drill Y Enabled Disabled P13 Relay Selection Y A B C D Module Y No Module Installed CRM4 CRPM Opt 1 CRPM Opt 2 Network Interface Card State Y Alarm Pre Alarm 1 Pre Alarm 2 Supervisory Trouble Process Zone Disable Release Pre discharge Abort Restart Delay Y 0 250 sec Silenceable Y Non Silenceable Silenceable Zone Ass...

Page 13: ... is the original Cheetah Xi format The ESP selection refers to an Expanded format Peripheral devices with 3 00 firmware or newer will used this command The EXP setting speeds up operation of the peripheral bus 3 If set to COMPACT a message filter within the panel is used to prevent transmission of certain history record events including the NEW DEVICE history messages This is done so that the peri...

Page 14: ...Address Y 000 000 000 000 User Defined 6 Supervision IP Address Y 000 000 000 000 User Defined 7 Panel IP Supervision Y 000 000 000 000 4 History Transmits Y 1 10 Fike recommends 2 Supervision Timeout Y 1 59 Sec Min Hour 4 min default IP Time Y IP Time Disabled Accept IP Time Send IP Time 8 Notes 1 Defines the location of the panel with respect to others on the network 2 Defines if the respective ...

Page 15: ... Y Acclimate 1 3 ft 3 6 ft High 2 0 Low 2 5 4 Y Day Night 1 3 ft 3 6 ft Day 3 6 Night 3 6 Y Alarm Supervisory Supervisory NL Drift Compensation Warning Trouble Y 50 100 Warning 80 Trouble 100 5 Walktest Y Walktest at Alarm Level Walktest with IR Walktest at 1 3 Device Summing Broadcast Thresholds for Summing OBS N Enabled Disabled 8 levels 0 5 ft 4 0 ft in 0 1 ft increments Summing Activation Leve...

Page 16: ... Y No State Alarm Summing Alarm Test Alarm Alarm Verification ON Pre Alarm 1 Pre Alarm 2 Supervisory Trouble Open Circuit Trouble Short Circuit Trouble Low Power Trouble Maintenance Trouble Process Zone Disable Switch Release Pre Discharge Abort Release Ckt Trouble Action Type Y No Action Activate on Any of 3 zones Activate on All of 3 zones Activate on Specific Device Activate on multiple priorit...

Page 17: ... 2 5 4 Y Day Night 1 3 ft 3 6 ft Day 3 6 Night 3 6 Y Alarm Supervisory Supervisory NL Flame Enhance N ON OFF Drift Compensation Warning Trouble Y 50 100 Warning 80 Trouble 100 5 Walktest Y Walktest at Alarm Level Walktest with IR Walktest at 1 3 Device Summing Broadcast Thresholds for Summing OBS N Enabled Disabled 8 levels 0 5 ft 4 0 ft in 0 1 ft increments Summing Activation Level OBS N 1 0 10 f...

Page 18: ...igh 2 0 Low 2 5 4 Y Day Night 0 8 ft 3 4 ft Day 1 5 Night 3 4 Y Alarm Supervisory Supervisory NL Drift Compensation Warning Trouble Y 50 100 Warning 80 Trouble 100 5 Walktest Y Walktest at Alarm Level Walktest with IR Walktest at 1 3 Device Summing Broadcast Thresholds for Summing OBS N Enabled Disabled 8 levels 0 5 ft 4 0 ft in 0 1 ft increments Summing Activation Level OBS N 1 0 10 ft 0 5 ft inc...

Page 19: ... Device 2nd Cross Zone Device Count Zone Device Single Release Device Alarm Verification Y Time 0 60 seconds Y Enabled Disabled Sensitivity Pre Alarm 1 2 Levels Y Enabled Disabled Y 70 F 190 F 5 F increments 3 Alarm Levels Day Night Y Fixed Temp 135 F 190 F 5 F increments 4 Y Rate of Rise 135 F 174 F 5 F increments 4 Walktest Y Walktest at 135 F Walktest with IR Remote Annunciator See Exhibit 2 7 ...

Page 20: ...s 4 Y Day Night 80 50 Microns 5 Micron increments Y Alarm Supervisory Supervisory NL N Smolder Enhance Off Smolder Enhance On Drift Compensation Y 50 100 Warning 80 Trouble 100 5 Walktest Y Walktest at Alarm Level Walktest with IR Walktest at 1 3 Device Summing Broadcast Thresholds for Summing OBS N Enabled Disabled 8 levels 0 5 ft 4 0 ft in 0 1 ft increments Summing Activation Level OBS N 1 0 10 ...

Page 21: ...ith Countdown Abort Watermist Activation Y Verify Time 0 255 seconds 3 Y Latching Non Latching 4 Y Normally Open Normally Closed 5 Y Class B Contact Class A Latching Class A Auto Restore Y No Short Detection Short Detection Notes 1 Cheetah Xi can have up to four 4 addressable loops 2 Can be assigned to 4 discrete zones 2 zone ranges or 1 range and 2 discrete zones 3 If monitor module function type...

Page 22: ...rmation Manual Alarm Stage 2 AHU Fire Dept Key Manual Release Manual Release with Countdown Abort Watermist Activation Y Verify Time 0 255 seconds 3 Y Latching Non Latching 4 Y Normally Open Normally Closed 5 Y No Short Detection Short Detection Notes 1 Cheetah Xi can have up to four 4 addressable loops 2 Can be assigned to 4 discrete zones 2 zone ranges or 1 range and 2 discrete zones 3 If monito...

Page 23: ...otes Defaults Pull Station Module Loop Number of Device Y 1 4 1 Address of Device Y 1 254 Custom Message Y 60 character user defined 1 001 PULL STATION Loop 1 Address 001 Custom Message Y Default User Defined Zone Assignments Y 1 254 2 Input Function Y No Input Function Manual Alarm Manual Release Manual Release with Countdown Notes 1 Cheetah Xi can have up to four 4 addressable loops 2 Can be ass...

Page 24: ...abled Disabled Output Control Activation State Y No State Alarm Summing Alarm Test Alarm Alarm Verification ON Pre Alarm 1 Pre Alarm 2 Supervisory Trouble Open Circuit Trouble Short Circuit Trouble Low Power Trouble Maintenance Trouble Process Zone Disable Switch Release Pre Discharge Abort Release Circuit Trouble Action Type Y No Action Activate on Any of 3 zones Activate on All of 3 zones Activa...

Page 25: ...m Summing Alarm Test Alarm Alarm Verification ON Pre Alarm 1 Pre Alarm 2 Supervisory Trouble Open Circuit Trouble Short Circuit Trouble Low Power Trouble Maintenance Trouble Process Zone Disable Switch Release Pre Discharge Abort Release Circuit Trouble Action Type Y No Action Activate on Any of 3 zones Activate on All of 3 zones Activate on Specific Device Activate on multiple priority rows activ...

Page 26: ...ults Releasing Module Common Loop Number of Device Y 1 4 1 Address of Device Y 1 254 Output Y Enabled Disabled Custom Message Y 60 character user defined 1 001 RELEASING MOD Loop 1 Address 001 Y Default User Defined Zone Assignments Y 1 253 3 zones available Output Type Y No Output Solenoid Expanded Solenoid Masterbox ARM IRM Expanded ARM IRM Watermist System Output State Y No Output State Alarm P...

Page 27: ...larm PreAlarm 2 PreAlarm 1 Supervisory Process 3 Y Latching Non Latching 4 Alarm Verification Timers Fire 2 Fire 1 Action 2 Action 1 Alert Y No Timer Timer 1 Timer 2 Timer 3 5 Verification Timer Values Timer 1 Timer 2 Timer 3 Y 0 255 seconds Acclimate Acclimate Y Enabled Disabled Acclimate High Range Y Range 1 H 0 00046 ft 0 04980 ft Range 2 M 0 05 ft 0 09982 ft Range 3 M 0 1 ft 0 99645 ft Range 4...

Page 28: ...itivity Y Yes No Miscellaneous Particulate Level Display Y Fire 2 Fire 1 Action 2 Action 1 Alert Air Flow Trouble Boundary Y 0 100 off normal 20 default Air Flow Trouble Timer Y 0 255 100 default Security Test Button Locked Y Enabled Disabled Isolate Button Locked Y Enabled Disabled Passcode Y 0 9999 1111 default Device Disable Isolate Button Y Enabled Disabled Reference Detector Analog Broadcast ...

Page 29: ...onfiguration Checksums Y Yes No Defaults Reset Default Config Reset All Default Device Configurations Y Yes No Defaults Custom Messages Panel LCD Custom Message Line 2 Logo Y 20 character user defined Fike Corporation Addressable Devices Restores all device custom messages to default Y Yes No Peripheral Devices Restores all device custom messages to default Y Yes No Air Sampling Devices Restores a...

Page 30: ...tdown Display Show Release Imminent Countdown Filter Y Show All Zone Countdowns Filter Countdown by Zone Do not show Countdown Programmable Key Functions 1 8 Y NO Function Reset Silence Acknowledge Drill Process Walktest IR Tool Step Alarm Step Supervisory Step Trouble Step All Fan Restart Zone Disable 1 Remote Display 2 and 10 Key Address Y 2 32 Custom Message Y 20 character user defined Fike Rem...

Page 31: ...ice Trouble Network Device Activation or Trouble Network Device Pre Alarm Network Device Activation or Pre Alarm Device selection Y PNL 1 128 Loop 1 4 Add 1 254 1 Activation State Y Alarm Pre alarm Process Trouble Supervisory Zone Disable Pre Discharge Release 2 Zone Assignments Y 1 254 2 Network Device selection Y PNL 1 128 Loop 1 4 Add 1 254 3 LED Illumination Pattern Active State Y Off Continuo...

Page 32: ...OK Activation State Y Alarm Pre Alarm Process Trouble Supervisory Zone Disable Pre Discharge Release 1 Zone Assignments Y 1 254 1 LED Illumination Pattern Active State Y Off Continuous Slow Blink Fast Blink Inactive State Y Off Continuous Slow Blink Fast Blink Silenced State Y Off Continuous Slow Blink Fast Blink Acknowledged State Y Off Continuous Slow Blink Fast Blink Multi Interface Module Addr...

Page 33: ...On Zone PreAlarm On Zone Alarm On Zone Predischarge On Zone Release On Zone Test Alarm On Zone Action On Panel Silence On Panel Drill On Panel Walktest On Panel Comm OK On Panel Power OK On Panel Buzzer Active On Any Network Device Active On Any Network Device Trouble On Any Network Device PreAlm On All Network Device Active Off Any Network Device Active Off All Network Device Active On Any LED Ac...

Page 34: ... Relay Modules All Releasing Modules All FAAST Sensors Y On Loop 1 4 Y Between 1 254 Y And 1 254 Y Select All Clear All Invert All Assignment by Zone Select Zones Y 1 254 Selection Options Y Select Clear Y All Zones Even Zones Odd Zones Y Between 1 254 Y And 1 254 Y Any Zone check box Y Select All Clear All Invert All Assignment by Network Device Select Network Devices Y 1 254 Example 002 1 001 Se...

Page 35: ...Trouble On Zone Supervisory On Zone Abort On Zone Disabled On Zone PreAlarm On Zone Alarm On Zone PreDischarge On Zone Release On Zone Test Alarm On Zone Action On Any Network Device On Any Network Device Trouble On Any Network Device PreAlm Off Any Network Device Off All Network Device 1 Assignment by Device Select Devices Y 1 254 Selection Options Y Select Clear Y All Addresses Even Addresses Od...

Page 36: ...1 254 Y And 1 254 Y Any Zone check box Y Select All Clear All Invert All Assignment by Network Device Select Devices Y 1 254 Select Options Y All Addresses Even Addresses Odd Addresses All Photo Sensors All Photo Heat Sensors All Photo Duct Sensors All Ion Sensors All Heat Sensors All Monitor Modules All Dual Monitor Modules All Mini Monitor Modules All Pull Station Modules All Conventional Zone A...

Page 37: ...e Device Count Zone Device Single Release Device Y Fire 1 Fire 2 2 Point ID Information Loop ID Y 1 4 3 Point ID Information Address ID Y 1 254 3 VESDA Scanner VESDA Zone Number Y 1 254 State Y Alarm Supervisory Trouble Device Enabled Y Enabled Disabled Custom Message Y 20 Characters user defined CUSTOM MESSAGE VZ001 Custom Message Y Default Custom Message User Defined Custom Message Zone Assignme...

Page 38: ...2 0 C Linx PROGRAMMING OPTIONS 2 30 Cheetah Xi Programming Manual Rev 1 09 2013 P N 06 651 Reserved for future use ...

Page 39: ...d when cycling through the event history The Step Alarm button only cycles forward in events These buttons allow you to go forward and backward through the events ESCAPE Press this key to toggle from Off Normal Event display if events are present to System Normal no events preset to Top Level Menu If in a menu this button EXITS the current menu and returns to the previous menu screen If in the Sys...

Page 40: ... a single System Administrator password to be assigned by the system installer The available security access levels are described as follows Password Level Designation Privileges Default door panel closed View system events on LCD display Access to STEP keys for reviewing system history 1 Customer door panel open no password entered All default privileges plus Access to system control switches for...

Page 41: ...HE SYSTEM ADMINISTRATOR PASSWORD After entering a successful Administrator level password you can change the default administrator password by changing the 4 digit number on the far right of Row B as shown in Exhibit 3 4 Use the navigation buttons to move the cursor under each field and the buttons to enter the new password cycles through 0 9 After completing the password change press the ENTER ke...

Page 42: ...the system device configurations For more extensive configuration changes you should use the C Linx configuration software to create a configuration template make necessary changes and upload the modified configuration back into the control panel LNote The drawback to using the AUTOPROGRAMMING method is that the devices are randomly addressed therefore you must document the actual location of each...

Page 43: ...to enter the systems PASSWORD entry screen and then enter a valid Level 3 password 3 Press the ESCAPE key to return to the TOP LEVEL MENU 4 Press the F1 key to enter the systems CONFIGURATION MENU 1 and then press the F6 key four times until the CONFIGURATION MENU 5 screen is displayed 5 Press the F2 key to enter the AUTO ADDRESSING screen 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A U T O A D D R ...

Page 44: ... D D R E S S B L O O P 1 A D D R E S S 0 0 1 C D P R E S S E N T E R T O S T A R T Exhibit 3 6 Device Address Screen Row B Use these fields to set the loop 1 5 and starting address number 1 254 to be assigned to the device Use the arrow keys to move the cursor under the Loop and Address fields then use the keys to increment decrement the fields Row D Press the ENTER key to start the automatic addr...

Page 45: ...B L E L O O P C P R E S S E N T E R W H E N D C O M P L E T E Exhibit 3 9 Connect Device Screen If the address change was successfully completed the following screen will be displayed 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A L O O P n A D D R E S S n n n B D E V I C E A D D R C H A N G E C C O M P L E T E D D E N T E R F O R N E X T D E V I C Exhibit 3 10 Address Change Completed Screen You are n...

Page 46: ... to communicate with the devices connected to the SLC Enabling the IR communication requires a Level 3 password Distributor Level To turn on IR Communication 1 Press the ESCAPE key until the Cheetah Xi s TOP LEVEL MENU is displayed 2 Press the F6 key to display the IR COMMUNICATION screen IR COMM 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A I R C O M M U N I C A T I O N B L O O P 1 D I S L O O P 2 D ...

Page 47: ... green pattern LNote There must be a clear line of sight between the IR tool and the device it is communicating with 3 The display will indicate 1 WRITE LOOP ADR Press the ENTER key 4 Use the number buttons to type in the desired Loop and Address number for the device Loops 001 004 Addresses 001 254 5 Point the IR tool at the device being addressed and press the ENTER key If the address is accepte...

Page 48: ...tion of the loop start up the following Device Address screen will be displayed 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A S E L E C T A D D R E S S B L O O P 1 A D D R E S S 0 0 1 C D P R E S S E N T E R T O S T A R T Exhibit 3 15 Device Address Screen Row B Use these fields to set the loop 1 5 and starting address number 1 254 to be assigned to the device Use the arrow keys to move the cursor und...

Page 49: ...B L E L O O P C P R E S S E N T E R W H E N D C O M P L E T E Exhibit 3 18 Connect Device Screen If the address change was successfully completed the following screen will be displayed 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A L O O P n A D D R E S S n n n B D E V I C E A D D R C H A N G E C C O M P L E T E D D E N T E R F O R N E X T D E V I C Exhibit 3 19 Address Change Completed Screen You are ...

Page 50: ...rom the communication port on the computer to the panel or the Hand Held Programmer when it instructs to connect the Serial Cable 8 C Linx will then request a password Type in the 4 digit password 9 The Status Message will display connection status Connect the device to be addressed 10 Once C Linx receives the NEW DEVICE record from the device it will highlight that TYPE of device in step 1 It wil...

Page 51: ...ammer to search for the devices attached Once it resets the loop of device s it will report each type of device with its loop number address number and serial number information 10 Select a specific row to modify then change the loop number and or address number in the bottom box Click Change Address to send the device the new loop and address number 11 Mark or label the device with the loop addre...

Page 52: ...3 0 GETTING STARTED 3 14 Cheetah Xi Programming Manual Rev 1 09 2013 P N 06 651 Reserved for future use ...

Page 53: ...ngs but restricts the settings that you are able to change See Section 3 2 1 for instructions on how to log onto the system 4 2 CONFIGURATION MENU 1 From the Top Level Menu screen press the F1 key to display the Configuration Menu 1 screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A C O N F I G U R A T I O N M E N U 1 B F 1 D E V I C E F 4 L E A R N C F 2 N A C F 5 D F 3 S L C F 6 M E...

Page 54: ...additional configuration options Row A Device Type Changes to display the type of device found at the selected loop address Photo Sensor Ion Sensor Photo Heat Sensor Heat Sensor Photo Duct Det Control Module Relay Module Monitor Module Mini Module and Pull Station Row B FUNC Allows you to change the function of the selected device address if applicable Use the arrow keys to position the cursor und...

Page 55: ...e or add the zone number LNote These programming options are typical for Photo Sensor Ion Sensor Photo Heat Sensor Heat Sensor and Photo Duct Detector B HOW TO MODIFY A CONTROL OR RELAY MODULE The default programming options for a sample control module are shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A 1 0 0 1 C O N T R O L M O D U L E B F U N C C C U S T O M M E S S A G E 1 0 0 1 D 0 0 0 0...

Page 56: ... On LTRB Low Power Trouble STRB Short Circuit Trouble OTRB Open Circuit Trouble MTRB Maintenance Trouble TSTA Test Alarm TRBL Trouble PROC Process PRA2 Pre Alarm 2 PRA1 Pre Alarm 1 SUPV Supervisory SUMA Summing Alarm ALRM Alarm ALRT Voice Alert EVAC Voice Evacuation PAGE Voice Page MSSA Mass Notification All Zones MSSZ Mass Notification by Zone 2ALL Page to Alert Page to EVAC Page All Page R R All...

Page 57: ...LTRB Low Power Trouble STRB Short Circuit Trouble OTRB Open Circuit Trouble MTRB Maintenance Trouble TSTA Test Alarm TRBL Trouble PROC Process PRA2 Pre Alarm 2 PRA1 Pre Alarm 1 SUPV Supervisory SUMA Summing Alarm ALRM Alarm ALRT Voice Alert EVAC Voice Evacuation PAGE Voice Page MSSA Mass Notification All Zones MSSZ Mass Notification by Zone 2ALL Page to Alert Page to EVAC Page All Page R R All ZDI...

Page 58: ...utput where X signifies 0 OFF F FAST 1 ON T TEMPORAL S SLOW W WALKTEST Use the arrow keys to position the cursor under pattern field then use the keys to change the activation pattern MODULE FUNCTIONALITY ROW ANDING This function setting requires all of the priority rows specified in Row D to become active before the control modules output will activate 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A 1 ...

Page 59: ...elds on this row allow you to select whether the module will be monitoring Normally Open NO or Normally Closed NC contacts Not all input functions provide the option of NO NC contacts as follows Pre Alarm I NO NC Supervisory NO Pre Alarm 2 NO NC Reset NO Man Alarm NO Silence NO NC Waterflow NO Acknowledge NO NC Pre Disch NO Drill NO NC Man Release NO Zone Disable NO NC Abort NO PAS Inhibit NO NC P...

Page 60: ...or under one of the zone number fields 000 then use the keys to change the zone number To add multiple zones move the cursor to the 2nd 3rd zone number fields then use the keys to change or add the zone number E HOW TO DELETE A DEVICE FROM THE SYSTEM CONFIGURATION You can delete a device from the system configuration by pressing the F1 key while viewing the device configuration The panel will disp...

Page 61: ...form the desired function READ Will take a copy of the configuration that the device holds and send it to the panel Read must be used prior to running a configuration check when any changes are made to the devices alarm features WRITE Will take the copy of the configuration that the panel holds for the device and send it to the device ENABLE DISABLE Lets you Enable Disable programmed SLC devices i...

Page 62: ...ure allows the startup of AHU s to be staggered From the Alarm Features screen select the address of the relay assigned to AHU shutdown then press the F3 key to access the AHU Re start Delay screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A H U R E L A Y R E S T A R T B D E L A Y 0 3 3 S E C O N D S C D Exhibit 4 14 Addressable Relay AHU Re start Delay Screen Row B This field allow...

Page 63: ...charge type A F for the selected device as described below Use the arrow keys to position the cursor under the field then use the keys to change the field value A Alarm Only No pre discharge in a zone will occur from the alarm of this device B Cross Zone B Pre discharge will occur in the zones assigned to this device when a corresponding C type is alarmed C Cross Zone C Pre discharge will occur in...

Page 64: ...s then use the keys to change to a different loop number or address number Device information for the address shown is then displayed if connected The device type field is not editable but will change for each device type found on the loop Row B Displays the panel and device checksum values for the device selected Row D Indicates progress of configuration check 4 2 2 HOW TO MODIFY THE PANEL S NAC ...

Page 65: ...e Alarm Pre Discharge Release Pre Alarm 1 Pre Alarm 2 Supervisory Trouble and Process Row C Protocol This field allows you to select whether the NAC circuit displayed in Row A will use the NAC protocol set for the panel see 4 2 2 3 or will activate constant Use the arrow keys to move the cursor to Row C then use the keys to change to the desired protocol LNote Both NAC 1 and NAC 2 must be set to t...

Page 66: ...s to toggle the field LNote The Any Zone option sets the selected NAC to activate on the configured state for any zone The Multi Zone option sets the selected NAC to activate on the configured state for any zone selected in Row D Row B This field allows you to set the 20 zone range that is displayed in Rows C D Use the arrow keys to position the cursor under the zone range field then use the keys ...

Page 67: ... key to access the SLC Configuration screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A U X I L I A R Y L O O P S B M O D U L E P R E S E N T N O C P A S N O A C K 1 5 0 0 0 0 D L O O P W I R I N G S T Y L E 4 Exhibit 4 21 SLC Configuration Screen Row B SLM This field allows you to turn on Supplemental Loop Module supervision Yes No If Yes is selected the panel will begin supervisin...

Page 68: ...nfiguration screen press the F1 key to access the SLC Command Mode screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A S T O R E T R O U B L E F O R N O B N E W D E V I C E E V E N T N O C S E N D A U T O C O M M A N D D A T M I D N I G H T N O Exhibit 4 22 SLC Command Mode Screen Row B This field allows you to set whether the panel will record a DEVICE NOT READY trouble for all output...

Page 69: ...figuration as needed using either the panel configuration menus or the C Linx programming software 4 2 4 1 LEARN New Devices Only The Learn New Device Only option will identify only new addressable devices connected to a signaling line circuit SLC New devices will be added to the panel s device supervision list New devices will operate with the default configuration held by the device until it is ...

Page 70: ...ress the Enter key 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A S E L E C T R E S E T M O D E B L E A R N A L L D E V I C E S C P R E S S E N T E R T O S T A R T D P A N E L W I L L R E S E T Exhibit 4 26 LEARN ALL DEVICES Screen The panel will reset and enter the Learn Mode 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A L E A R N M O D E I S A C T I V E B W A I T T O C O M P L E T E C 0 9 2 7 4 7 A 0 3 1...

Page 71: ... 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A T I M E H H M M S S A M B D A T E M M D D Y Y Y Y C D A Y D A Y O F W E E K D D A Y L I G H T S A V I N G S Y E S Exhibit 4 29 Time Control Screen Row A This field allows you to set the Hour HH Minute MM Second SS and AM PM values for the system Use the arrow keys to position the cursor under the field then use the keys to increment decrement the field to a diffe...

Page 72: ...ence the panel for one minute following the receipt of the first alarm event Row A REM This field allows you to turn the system Silence Reminder On Off Use the arrow keys to position the cursor under the field then use the keys to toggle status This feature requires that the panel produce a momentary pulse from the panel piezo buzzer following the silencing of outputs If this is configured to be O...

Page 73: ...e AC input terminal 120 240VAC Use the arrow keys to position the cursor under the field then use the keys to toggle status I CAUTION Selecting the incorrect transformer size could result in erratic panel trouble conditions Row C The BATTERY MAIN field allows you to turn on off supervision of the Main controller Battery Input terminals Yes No Use the arrow keys to position the cursor under the fie...

Page 74: ...ity setting is to be used must be configured Sensors enabled for daytime sensitivity will change to Day Alarm level when the start time is reached and revert back to Night Alarm level when the stop time is reached From the Daytime Sensitivity Menu screen press F1 to access the Daytime Sensitivity Range screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A D A Y T I M E S E N S I T I V I ...

Page 75: ...on arrow 4 3 5 HOW TO ENABLE DISABLE AND ASSIGN CUSTOM MESSAGES TO ZONES The Zone Configuration screen allows you to enable disable and assign a custom message to any of the Cheetah Xi s 254 available operating zones From the Configuration Menu 2 screen press the F5 key to access the Zone screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A Z O N E 0 0 1 E N A B L E D B C U S T O M M E ...

Page 76: ...e zone displayed in Row B Use the arrow keys to position the cursor under the field then use the button to select the digit range from 0 to 9 If a three digit chime code is required the fourth field must be left at 0 The codes chime at 1 second intervals The time between digits is roughly 2 seconds The time between a 3 and 4 digit signal is about 6 seconds Row D Displays the number of zones that h...

Page 77: ...bort Configuration Screen F5 Day Night Sensitivity Enable Disable F6 Configuration Menu 4 4 4 1 HOW TO SET PERIPHERAL DEVICE PARAMETERS The Peripherals Menu provides access to configuration parameters associated with the selected panel s 31 possible peripheral devices From the Configuration Menu 3 screen press the F1 key to access the Peripheral Menu screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3...

Page 78: ... LED Graphic Remote Display 10 Key Remote MIC Zone Graphic Remote Display 2 Key Print Serial Switch 20 Zone Bosch DACT Annunciator 20 Zone Print Parallel Computer Precise Vision Print Gateway Amplifier Gateway Only Relay Control Press the F1 key to display additional configuration options See 4 4 1 1 2 Press the F1 F2 or F3 keys to perform peripheral device tests See 4 4 1 1 1 Press ENTER to displ...

Page 79: ...eral device to perform a checksum calculation on its configuration memory The feedback message CHECKSUM CALC will be indicated on Row D of the display as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A P E R I P H E R A L A D D R 0 2 B T Y P E S M O K E C O N T R O L C S U P E R V I S E Y E S Z 0 0 0 D C H E C K S U M C A L C Exhibit 4 42 Checksum Calc Screen 4 4 1 1 2 HOW TO PROGRAM A 256 L...

Page 80: ...rals jack to transmit the device configurations USB CONNECTOR mode is used for Cheetah Xi 50 peripheral device configuration In this mode peripheral device configurations are transmitted during the panel configuration process via the panel s P3 PC USB jack You must keep the cable in the USB port enter the Level 3 password at the panel and go to this menu to re direct the configuration information ...

Page 81: ...ility of peripheral devices released with firmware versions older than v3 0 If any device on the peripheral bus has firmware older than v3 0 the STD option must be used Row B The HISTOR XMIT field allows you to change RS485 transmission protocol from COMPACT VERBOSE COMPACT This protocol is provided as a means to decrease data traffic on the peripheral bus Any history event created at the panel th...

Page 82: ... ENABLE DISABLE SYSTEM GROUND FAULT DETECTION The Ground Fault screen reflects the current state of the two Ground Fault levels detected by the panel From the Configuration Menu 3 screen press the F3 key to access the Ground Fault screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A G N D F A U L T S U P E R V I S E B L E V E L 1 E N A B L E D C L E V E L 2 E N A B L E D D O F F S E T 0...

Page 83: ...during pre discharge the release cannot again be aborted so release occurs upon countdown completion Type 2 Countdown continues during abort activation Release occurs when both the countdown is completed and the abort is deactivated Type 3 If the abort is active during pre discharge release occurs upon abort deactivation Type 4 If the abort is active during pre discharge release occurs 10 seconds ...

Page 84: ...elect the Enable Disable status of Day Night Sensitivities Use the keys to toggle the field status ENABLED DISABLED Row D Displays the current Sensitivity being used due to the time of day and day night changeover times 4 5 CONFIGURATION MENU 4 From the Configuration Menu 3 screen press the F6 key to access the Configuration Menu 4 screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A C ...

Page 85: ...ue Enter 0 for no delay or enter a number 01 30 hours to provide a delay for the trouble to be transmitted to the DACT 4 5 2 HOW TO CONFIGURE VESDA DETECTORS The VESDA Configuration options let you change the operating parameters for the air sampling detectors connected to the panel From the Configuration Menu 4 screen press the F2 key to access the VESDA Configuration Menu screen as shown below 1...

Page 86: ...associated with the selected zone number from Row A Use the arrow keys to position the cursor under the field then use the keys to select the desired detector type The ALM field allows you to select the state of operation for the detector ALM default Use the arrow keys to position the cursor under the STATE field then use keys to select the state of operation for the detector The ENA field allows ...

Page 87: ...P ADDR The EVAX option lets you configure the VESDA to report as a virtual address on the Cheetah Xi addressable loop This option is used if the VESDA needs to be monitored by a point ID system i e EVAX DACT LED Graphic Computer Graphic etc From the VESDA Configuration Menu screen press the F3 key to access the VESDA Loop Address screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A V E ...

Page 88: ...om the alarm of this device B Cross Zone B Pre discharge will occur in the zones assigned to this device when a corresponding C type is alarmed C Cross Zone C Pre discharge will occur in the zones assigned to this device when a corresponding B type is alarmed D Counting Zone Pre discharge will occur when two or more D types are alarmed in the assigned zones E Single Pre discharge Only one alarmed ...

Page 89: ...re version 3 08 00 or higher PEER TO PEER OLDER Allows communication with up to 40 VESDA units but only 10 can be connected to the HLI and still meet UL and NFPA s 10 second supervision response time HLI firmware versions older than 3 08 00 4 5 3 HOW TO CONFIGURE AUXILIARY POWER CIRCUTS AS AUX NACS The Aux NAC option lets you configure the Cheetah Xi s auxiliary power circuits for use as notificat...

Page 90: ...nfiguration options become available on Row D 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A U X N A C 3 E N A B L E D B S T A T E A L A R M C P R O T O C O L C L A S S B N A C D S I L N D R I L L N W A L K N Exhibit 4 61 AUX NAC Functions Screen Row B This field allows you to select the circuits operational state i e Alarm Pre Alarm 2 Process Trouble Supervisory and Pre Alarm 1 Use the arrow keys to...

Page 91: ...on sets the selected circuit to activate on the configured state for any zone selected in Row D Row B These fields allow you to set the 20 zone range that is displayed in Rows C D Use the arrow keys to position the cursor under the zone range field then use the keys to increment decrement the group of 20 forward or backwards Zones 001 254 Row C These numbers act as placeholders and zone number ind...

Page 92: ...s to move the cursor under the loop and address fields then use the keys to increment decrement the fields LNote The addressable relay module contacts will transfer and latch when a panel voltage trouble is recorded The relay contacts will remain latched even if the panel power is removed 4 5 5 HOW TO CONFIGURE PANEL RELAYS AND OPTIONAL MODULES The Relay options menu lets you change the programmin...

Page 93: ... A T B P 1 2 B O S C H D A C T C P 1 3 C R M 4 D Exhibit 4 65 Select Module Screen Row B This field allows you to select the module that is present at location P12 No Module CRM4 RPM 1 RPM 2 Bosch DACT Use the arrow keys to move the cursor under the field then use the keys to select a different module Row C This field allows you to select the module that is present at location P13 No Module CRM4 R...

Page 94: ...rameters can not be changed Row B This field allows you to set the relay activation state i e Alarm Pre Discharge Release Pre Alarm 2 Process Trouble Supervisory Abort Zone Disable Pre Alarm 1 for the relay selected in Row A Use the arrow keys to move the cursor under the field then use the keys to toggle the desired state Row C This field allows you to set the Silenceable and Drill Enabled Disabl...

Page 95: ...ANY ZONE or MULTI ZONE LNote The Any Zone option sets the selected relay to activate on the configured state for any zone The Multi Zone option sets the selected relay to activate on the configured state for any zone selected in Row D Row B This field allows you to set the 20 zone range that is displayed in Rows C D To change the zone range use the arrow keys to position the cursor under the zone ...

Page 96: ...ns and fan restart relays will deactivate according to their programmed time delay MANUAL Upon activation of an ALARM event the CRM4 relays will activate and remain active until panel is reset After panel reset the fan restart sequence is delayed until the operator activates any of the following switch sources 1 Panel s ENTER key 2 monitor module configured for Fan Restart 3 RDU switch configured ...

Page 97: ...le devices connected to a Signaling Line Circuit SLC with either a Loop 0 or Address 0 configuration New device will be assigned the next available address From the Configuration Menu 5 screen press the F2 key to access the Auto Address screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A U T O A D D R E S S I N G O F F B S E L E C T L O O P S 1 2 3 4 C S E L E C T A D D R S 0 0 1 0 5...

Page 98: ... daily dialer test Configurable between 0 and 23 hours where the default is 2 AM Use the arrow keys to move cursor to the field then use the keys to increment decrement the time LNote The Contact ID dialer is capable of performing its own operational tests Configuring the panel to initiate its own test might be redundant and could be considered a nuisance to the monitoring company Only utilize thi...

Page 99: ...the button to increment decrement the range in groups of 20 forward or backwards ID s 001 128 Row C These numbers act as placeholders and zone number indicators for the range of zones selected on Row B Row D These fields allow you to select the Network panel ID s to be supervised by this panel The fields show the panel IDs on the network in groups of 20 Move the cursor with the arrow keys to posit...

Page 100: ...rovide assistance in diagnostics MIDDLE If the Cheetah Xi network has more than two panels maximum of 128 every panel on the network not configured as either a First or Last must be configured as Middle or None LAST A Cheetah Xi network must have at least two panels One of the two panels regardless of wiring style must be configured as the Last panel This requirement is present to provide directio...

Page 101: ...l deselect all zones Row C These numbers act as placeholders and zone number indicators for the range of zones selected on Row B Row D This range of fields allows you to select the zones that the specific panel will react to Blank will ignore events in this zone Y will react to events in this zone Use the arrow keys to position the cursor under the specific zone field then use the keys to toggle t...

Page 102: ... screen is dependent upon the switch function setting Local or Global in the Network Module Configuration screen See Section 4 6 4 2 From the Network Configuration Menu press the F5 key to access the Network Switch screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A C C E P T S W I T C H E S F R O M B N E T W O R K I D S 0 0 1 0 2 0 C 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 D Y y Y Y...

Page 103: ...keys to increment decrement the field Row C The HIST History field allows you to set the unique Internet Protocol IP Address of the panel that will receive history messages from this panel Use the arrow keys to position the cursor under the field then use the keys to increment decrement the field LNote The History IP Address should equal the Source IP Address of the receiving panel Row D The SUPV ...

Page 104: ...ow B This field allows you to select the Panel ID to supervise Use the arrow keys to position the cursor under the field then use the keys to increment decrement the field to select panel from 001 128 Row D This field allows you to enter the Source IP Address for the panel ID selected in Row B Use the arrow keys to position the cursor under the field then use the keys to increment decrement the fi...

Page 105: ...18 hours 1 hour increments LNote This parameter only applies when the respective panel is configured to supervise other panels Row C This field allows you to set how many times a single history event will be transmitted to the peripheral bus This setting greatly affects the reliability of the Ethernet reporting system The value can be configured from 1 to 10 1 Provides the greatest amount of speed...

Page 106: ...Silence keys between NORMAL DISABLED LNote If the panel is ordered with the COC extension in the part number it will be shipped with a display that has the Drill and Silence keys blanked out The functionality of these keys will be disabled and will require a factory level password to re enable 4 7 5 HOW TO SET PANEL S LED OPERATION The LED Operation screen allows you to set the panel s LEDs to fun...

Page 107: ... HOW TO ENABLE AHU KEY REQUIREMENT FEATURE The AHU Key screen allows you to set the FAN RESTART configuration parameters for the panel to require activation of an AHU FIRE KEY input before initiation of the fan restart sequence is allowed From the Configuration Menu 7 screen press the F1 key to access the AHU Key screen as shown below 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 A A H U K E Y R E Q U I...

Page 108: ...4 0 CONFIGURATION MENU 4 56 Cheetah Xi Programming Manual Rev 1 09 2013 P N 06 651 Reserved for future use ...

Page 109: ...DEVICE TROUBLE F4 LEARN F5 VOICE F1 MNS RESET F2 PRIORITIES F6 MENU 2 CONFIGURATION MENU 2 2 4 F1 TIME F2 SILENCE F3 POWER F4 DAY SEN F1 DAYTIME SEN RANGE F2 SELECT HOLIDAYS F5 ZONE F1 SIGNAL CODE F2 EVACUATE SETS F6 MENU 3 CONFIGURATION MENU 3 2 4 F2 HISTORY HISTORY MENU F1 PERIPH F1 DEVICE F1 ALARM 1 4 F2 SOURCE F2 SUPERV 1 4 F3 SPEED F3 TROUBL 1 4 F2 WALK F4 CMD SET F4 EVENTS 1 4 F3 GROUND 4 F5...

Page 110: ...ORK F1 ID S F1 CUSTOM MESSAGE F4 HISTORY 1 4 F2 MODULE F5 BRD COM 1 4 F3 ZONES F5 SELECT ALL F6 MENU 4 DIAGNOSTIC MENU 4 F6 DESELECT ALL F1 AMP STA 1 4 F4 HIST TR F2 PER DAT 1 4 F5 SWITCH F1 CUSTOM MESSAGE F6 MENU 6 CONFIGURATION MENU 6 2 4 F3 VOICE Z 1 4 F1 VOICE STATUS F1 IP ADR F1 CLR IP ADDR HIST F4 PER FV 1 4 F2 IP SUP F1 CUSTOM MESSAGE F5 F3 IP TIM F6 MENU 5 DIAGNOSTIC MENU 5 F4 SW OPER4 F1 ...

Page 111: ......

Page 112: ...704 SW 10th Street P O Box 610 Blue Springs Missouri 64013 Tel 816 229 3405 Fax 816 229 0314 www fike com ...

Reviews: