2.0 C-Linx PROGRAMMING OPTIONS
2-4
Cheetah Xi Programming Manual
Rev 1, 09/2013
P/N: 06-651
Exhibit 2-3: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Relays
P12
Relay Selection
Y
A / B / C / D
Module Y
No Module Installed /
CRM4
/
CRPM (Opt 1) / CRPM (Opt
2) / Fire Communicator
State
Y
Alarm / Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / Zone
Disable / Release / Pre-
discharge / Abort
Restart Delay
Y
0
– 250 (sec)
Silenceable Y
Non-Silenceable
/
Silenceable
Zone Assignment
Y
1 –
254
Relay Y
Enabled
/ Disabled
Drill Y
Enabled
/ Disabled
P13
Relay Selection
Y
A / B / C / D
Module Y
No Module Installed /
CRM4
/
CRPM (Opt 1) / CRPM (Opt
2) / Network Interface Card
State
Y
Alarm / Pre-Alarm 1 / Pre-
Alarm 2 / Supervisory /
Trouble / Process / Zone
Disable / Release / Pre-
discharge / Abort
Restart Delay
Y
0
– 250 (sec)
Silenceable Y
Non-Silenceable
/
Silenceable
Zone Assignment
Y
1 –
254
Relay Y
Enabled
/ Disabled
Drill Y
Enabled
/ Disabled
Zones Zones
Y
1 –
254
Type Y
Alarm Zone
/ Count Zone /
Cross Zone / Single Sensor
Release Zone
Custom Message
Y
20 character user defined
Automatic Countdown
Y
0 – 255
(30)
Manual Countdown
Y
0 – 30
(15)
Zone Enabled
Y
Enabled
/ Disabled
Zone Chimes
Y
Assign chime code to zones
Summary of Contents for 10-068
Page 111: ......