2.0 C-Linx PROGRAMMING OPTIONS
Cheetah Xi Programming Manual
2-11
P/N: 06-651
Rev 1, 09/2013
Exhibit 2-10: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Heat
Sensor)
Common
Loop Number of Device
Y
1 -
4
1
Address of Device
Y
1
– 254
Custom Message
Y
60 character user defined
(1-001 HEAT DETECT
Loop 1 - Address 001)
Y
Default /
User Defined
Zone Assignments
Y
1
– 254
2
Predischarge Type
Y
Auto Assign From 1
st
Zone /
Alarm Only Device
/ 1
st
Cross Zone Device / 2
nd
Cross Zone Device / Count
Zone Device / Single Release
Device
Alarm Verification
Y
Time: 0 – 60 seconds
Y
Enabled
/ Disabled
Sensitivity
Pre-Alarm 1 & 2 Levels
Y
Enabled
/ Disabled
Y
70°F -
190°F
(5°F increments)
3
Alarm Levels (Day/Night)
Y
Fixed Temp:
135°F
- 190°F
(5°F increments)
4
Y
Rate of Rise:
135°F
- 174°F
(5°F increments)
4
Walktest Y
Walktest at 135°F
/ Walktest
with IR
Remote Annunciator (See Exhibit 2-7 for programming features)
Notes:
1.
Cheetah Xi can have up to four (4) addressable loops.
2.
Can be assigned to 4 discrete zones, 2 zone ranges or 1 range and 2 discrete zones.
3.
Pre-Alarm 2 setting must always be set equal or higher than Pre-Alarm 1 setting.
4.
Rate of Rise temperature range is 135°F - 174°F. Fixed temperature operation will be used for detection above this range.