2.0 C-Linx PROGRAMMING OPTIONS
Cheetah Xi Programming Manual
2-17
P/N: 06-651
Rev 1, 09/2013
Exhibit 2-16: Programming Features Cont.
Circuit or
Component
Program Feature or Option
Permitted
in UL
864?
(Y/N)
Possible Settings
(Defaults shown bold)
Settings
permitted
in UL 864
Notes
Defaults
(Relay
Module)
Common
Loop Number of Device
Y
1 -
4
1
Address of Device
Y
1
– 254
Output Y
Enabled
/Disabled
Custom Message
Y
60 character user defined
(1-001 RELAY MODULE
Loop 1 - Address 001)
Y
Default/
User Defined
Zone Assignments (Device
Troubles)
Y
1
– 253
(4 zones available)
AHU Shutdown Relay
Y
Enabled /
Disabled
Restart Delay
Y
0
– 255 seconds
4
Misc. Options
(feedback relay monitoring)
Y
Not Monitored
/ Monitored
by dry contact / Independent
dry contact
5
Positive Alarm Sequencing
(PAS)
Y
Enabled /
Disabled
5
Output Control (Note 6)
Activation State
Y
Alarm
/ Summing Alarm /
Test Alarm / Alarm
Verification ON / Pre-Alarm 1
/ Pre-Alarm 2 / Supervisory /
Trouble / Open Circuit
Trouble / Short Circuit
Trouble / Low Power Trouble
/ Maintenance Trouble /
Process / Zone Disable
Switch / Release / Pre-
Discharge / Abort / Release
Circuit Trouble
Action Type
Y
No Action /
Activate on Any
of 3 zones
/ Activate on All of
3 zones / Activate on Specific
Device / Activate on multiple
priority rows active
Relay State
Y
ON
/ OFF / Timed / Time
Delay
Timeout Y
0
– 80 minutes
2
State Counter
Y
1
– 16
Output Y
Silenceable
/Non-Silenceable
Drill Y
Enabled
/ Disabled
Zone Assignments (activation)
Y
0
- 255
3
Notes:
1.
Cheetah Xi can have up to four (4) addressable loops.
2.
Timeout delay becomes active if relay state is set to ‘Time Delay’.
3.
Can be assigned to any 3 zones, 254 any zone, or 255 any zone (non-disable).
4.
Restart delay becomes active if relay is configured for AHU shutdown operation.
5.
These options are not available if relay is configured for AHU shutdown operation.
6.
Output control is disabled if relay is set for AHU Shutdown operation.