3.0 GETTING STARTED
3-6
Cheetah Xi Programming Manual
Rev 1, 09/2013
P/N: 06-651
3.4.2 HOW TO USE THE PANEL’S DEVICE ADDRESS FUNCTION TO ADDRESS A DEVICE
This method allows you to take a field device straight out of the box and connect it to the panel’s signaling line
circuit (SLC) to be addressed. The Device Address (DEV ADR) function when activated, allows the panel to
automatically assign an address to each new device as it is connected to the panel’s signaling line circuit
(SLC).
To Address devices:
1. Press the ESCAPE key until the Cheetah Xi’s TOP LEVEL MENU is displayed.
2. Press the F5 key to enter the systems MAINTENANCE MENU.
3. Press the F2 key to enter the DEVICE ADDRESS screen (DEV ADR).
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A S E L E C T
A D D R E S S
B L O O P : 1
A D D R E S S : 0 0 1
C
D P R E S S
E N T E R
T O
S T A R T
Exhibit 3-6: Device Address Screen
•
Row B – Use these fields to set the loop (1 – 5) and starting address number (1 – 254) to be
assigned to the device. Use the
◄►
arrow keys to move the cursor under the Loop and Address
fields; then use the +/- keys to increment/decrement the fields.
•
Row D - Press the ENTER key to start the automatic address function.
4. Once the chosen loop and address is set, press the ENTER key to start the automatic address function.
The following Connect Device screen will be displayed.
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A C O N N E C T
D E V I C E
T O
B A D D R E S S A B L E
L O O P
C P R E S S
E N T E R
W H E N
D C O M P L E T E
Exhibit 3-7: Connect Device Screen
•
Attach sensors to the integral base on the programmer.
•
Attach modules to the programmer using the supplied wire leads (Red wire to Loop positive
connection; Black wire to Loop negative connection).