background image

Table A

If the code letter on

your existing

Thermostat is

then mark the wire

with label shown

and connect to

thermostat terminal

shown

Mount wallplate and Thermostat

 Remove the wallplate from your thermostat. See Figure 2.

Figure 2

 Position wallplate on wall and pull existing wires through large opening.

Then  level  for appearance. Mark  holes  for  plastic  anchors  provided,  if

your existing holes do not line up with those on the wallplate.

 Drill holes with 3/16” bit and gently tap anchors into the holes until flush

with wall.

  Reposition  wallplate  to  wall,  pulling  wires  through  large  opening.  Insert

mounting screws provided into wall anchor and tighten. See Figure 3.

Figure 3

NOTE: 5- Wire Systems

If your thermostat has one wire marked R or Rh (2, 3, or 4-wire system),

then  leave  the  jumper  wire  between  the  Rh  and  Rc  terminals  on  the

wallplate. Otherwise, if you have separate Rh and Rc wires (5-wire system),

then remove the jumper wire between the Rh and Rc terminals.

Connect Wires and Mount Thermostat to wallplate

 Match  and connect  the  labeled  wires  to the appropriate  coded  terminal

screws on the wallplate. (See Figure 4, 5.) Ignore any wires which may

be present, but which were note connected to the old thermostat.

Figure 4

                      Figure 5

  Refer  to  the  Wiring  Diagrams  below  to  be  sure  your  system  is  wired

correctly.

 If your system is a single stage heat pump and uses an O or B wire, you

must move the  System Selector switch  inside  the thermostat to the  Heat

Pump position. If you have a normal furnace or electric system, leave the

switch in the Standard position. Refer to the System Selector section on the

back for more information on this switch.

  Be sure to tighten the terminal screws  securely, otherwise  a  loose  wire

could cause operational problems with your system or thermostat.

  Push  excess  wire  back  into  the  hole  to  prevent  interference  when

installing the thermostat to the wallplate.

 Make sure the System Switch is set to OFF, and the Fan Switch is set to

AUTO.

Insert the tabs on top of the thermostat body into the slots at the top of the

wallplate.  Press  the  bottom  of  the  thermostat  body  into  the  snap  on  the

bottom  of  the  wallplate.  Refer  to  Figure  2.  (NOTE:  Do  not  force  the

thermostat onto  the  wallplate,  as the terminal  pins may be  damaged. If  it

does not snap properly, the thermostat may not work.)

  Insert  the  two  AA  size  alkaline  batteries,  observing  the  polarity  marked

inside the battery compartment.

 Switch on the main power at the panel or furnace.

Wiring Diagrams

X-No Connection

Selector Switches

In order for this thermostat to control your system, the system type must be

specified  by  the selector  switches  on  the  printed  circuit  board  inside  the

thermostat. There is also a selector switch for your choice of Fahrenheit or

Celsius temperature display. See figure 6.

Heating System Selector (HG – HE switch)

The factory position for this switch is in the “HG” position. Leave it in this

position if you have a gas furnace or an oil burner. If you have an electric

furnace, test to see whether the Heat and Fan come on as expected after

installation. If the Fan operation is normal, leave it in the “HG” position. If

the  Fan  does  not  come  on  within  a  minute  of  the  thermostat  calling  for

heating,  change  the  switch  position  to “HE”.  The  system  selector  has  no

effect in the cooling mode.

NOTE: “HG” position is for gas and most other systems. “HE” position is for

certain electric systems having a fan relay.

System Selector (STANDARD – HEAT PUMP switch)

The factory  position for this  switch  is  in the  STD  position. Leave  it  in  this

position  if  you  have  ANY system  that  uses  gas,  oil, electric,  or  hot  water

heating. If you have a single-stage Heat Pump (no auxiliary or emergency

heat source), then slide the switch to the HP position. Be sure the reversing

valve wire is connected to the correct terminal for your heat pump (Rc/O) or

(Rh/B).

˚F / ˚C selector (Fahrenheit / Celsius)

Your thermostat is set for ˚F mode from the factory. In order to change to ˚C

mode, slide the switch to ˚C and hold any key about 2 seconds without the

battery, then place the battery again.

NOTE:  Unless  press  any  key  about  2  seconds  without  the battery,  then

place the battery again.

Figure 6

TROUBLESHOOTING

Problem

Solution

1. Check battery connections and batteries.

No Display

2.  Move  the  battery  out  and wait  for  about  1

minutes then Replace Batteries..

Entire Display

Dims.

1. Replace Batteries.

Auto Fan Does Not

Turn On Properly.

1. Move HG/HE selector to correct position.

1. Check that the function switch is in the correct

position (“HEAT” or “COOL”).

2.  There  may  be  as  much  as  4-mintue  delay

before the system turns On – wait and check.

(Compressor protection delay.)

3.  Check  your  circuit  breakers  and  switches  to

ensure there is power to the system.

4. Replace batteries.

5. Make sure your furnace blower door is closed

properly.

6.  If  your  non-heat  pump  system  only  uses

4-wires,  be  sure  the  jumper  wire  is  installed

between the Rh/B and Rc/O terminals.

7.  Check  the  position    of  the  Reversing  Valve

selector switch: Standard or Heat Pump.

Heating  or  Cooling

Does Not Go On or

Off.

8.  If  you  have  single-stage  heat  pump,  be  sure

the jumper wire is installed between the Y and

W terminals.

Erratic Display

1. Move the battery out hold any key then place

the battery again. Then reprogram.

If unit continues to

operate in the Off

position.

1. Replace unit.

Thermostat

permanently reads

  “HI”,

“LO”,

or

“E1” ,   “E2”.

1. Replace unit.

L

N

Rh

H

E

H

G

C

C

C

C

C

C

Reviews: