REcOMMENdEd MINIMuM WIRE GAuGE fOR EXTENSION cORdS*
(120 OR 240 VOlT)
NAMEPlATE
AMPERES
(at full load)
EXTENSION cORd lENGTH
25 feet
50 feet
75 feet
100 feet 150 feet
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3.5 – 5.0
18
18
16
14
12
5.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
TAblE A
* based on limiting the line voltage drop to five volts at 150% of the rated amperes.