SKU 95091 For technical questions, please call 1-800-444-3353 PAGE 8
only wire connected to the tool’s grounding system and must never be attached
to an electrically “live” terminal. (See Figure B.)
3.
The Chipper/Shredder must be plugged into an appropriate outlet, properly
installed and grounded in accordance with all codes and ordinances. The plug
and outlet should look like those in the following illustration. (See Figure B.)
THIS PRODUCT
USES A
3-PRONG PLUG
FIGURE B
120 VOLT
GROUNDED
ELECTRICAL OUTLET
EXTENSION CORDS
1.
Grounded tools require a three wire extension cord. Double Insulated tools
can use either a two or three wire extension cord.
2.
As the distance from the supply outlet increases, you must use a heavier gauge
extension cord. Using extension cords with inadequately sized wire causes a
serious drop in voltage, resulting in loss of power and possible tool damage.
(See Figure C, next page.)
3.
The smaller the gauge number of the wire, the greater the capacity of the cord.
For example, a 14 gauge cord can carry a higher current than a 16 gauge cord.
(See Figure C, next page.)
4.
When using more than one extension cord to make up the total length, make
sure each cord contains at least the minimum wire size required.
(See Figure C, next page.)
5.
If you are using one extension cord for more than one tool, add the nameplate
amperes and use the sum to determine the required minimum cord size.
(See Figure C, next page.)
6.
If you are using an extension cord outdoors, make sure it is marked with the
suffix “W-A” (“W” in Canada) to indicate it is acceptable for outdoor use.
7.
Make sure your extension cord is properly wired and in good electrical condition.