Page 9
SKU 96448
For technical questions, please call 1-800-444-3353.
Make sure the extension cord is properly wired and in good electrical condition.
7.
Always replace a damaged extension cord or have it repaired by a qualified elec
-
trician before using it.
Protect the extension cords from sharp objects, excessive heat, and damp or wet
8.
areas.
reCommended minimum wire gauge For eXtension Cords*
(120/240 Volt)
nameplate
amperes
(at full load)
eXtension Cord length
25 Feet
50 Feet
75 Feet
100 Feet
150 Feet
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3.5 – 5.0
18
18
16
14
12
5.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
taBle a
* Based on limiting the line voltage drop to five volts at 150% of the rated amperes.
symbology
Double Insulated
V~
Volts Alternating Current
Canadian Standards Association
a
Amperes
Underwriters Laboratories, Inc.
n0 xxxx/min.
No Load revolutions per Minute
(rPM)