< 100 A: use AWG8
< 200 A: use AWG6
< 300 A: use AWG4
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is recommended).
Example of supply cable calculation:
I
tot
= 128 A, maximum ambient temperature is 45 °C,
recommended fuse = 150 A
• Single supply cables (3 1 PE - configuration (1)):
• I = 128 A + 25 % = 128 x 1.25 = 160 A
• For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
• Install the prescribed maximum fuse (150 A) on each cable
• Parallel supply cable (2 x 3 2 PE - configuration (2)):
• I = (128 A + 25%)/2 = (128 x 1.25)/2 = 80 A
• For a AWG4, the maximum current is 85 A x 0.8 = 68 A, which is insufficient. For an AWG3,
the maximum current is 100 x 0.8 = 80 A. So 2 parallel cables of 3 x AWG3 + 2 x AWG8 are
sufficient.
• Install 80 A fuses on each cable.
• Recommended fuse values are based on full service factor and 10% under- and
over-voltage.
•
Causion:
Always double check the fuse size against the calculated cable size.If required,
increase the cable size.
9.2
Reference conditions and limitations
Reference conditions
Air inlet pressure (absolute)
bar
1
Air inlet pressure (absolute)
psi
14.5
Air inlet temperature
˚C
20
Air inlet temperature
˚F
68
Relative humidity
%
0
On water-cooled units also:
Cooling water inlet temperature
˚C
20
Cooling water inlet temperature
˚F
68
Limits
Maximum working pressure
Minimum working pressure
bar(e)
4
Minimum working pressure
psig
58
Maximum air inlet temperature
˚C
46
Instruction book
92
2920 7101 41