• This screen shows the minimum stop time (20) and the unit <s> (seconds).
• To modify this value press the Enter button (13). The value starts blinking and Scroll buttons (12) can
be used to modify this value.
• Press Enter button (13) to program the new value.
The minimum and maximum values depend on the parameters.
3.28 Activating password protection
Important settings such as the setting of the service timer, pressure band setting, control mode settings,...
can be protected by a password.
Starting from the Main screen:
• Press Scroll buttons (12) until <P.13> is shown and press Enter button (13):
• Password (<PASS>) appears on the screen. Press the Enter button (13).
• The screen shows the password status (ON (<On>) or OFF (<OFF>). Press Enter button (13) to
modify.
• Change the value with Scroll buttons (12).
• Select <On> and press Enter button (13).
• Enter the new password and press Enter button (13) to confirm.
• Enter the password again and press Enter button (13) to confirm.
• <On> appears on the display. Press reset key to return to the parameter screen.
Lost passwords can not be recovered. Save the password carefully.
3.29 Activate load/unload remote pressure sensing
Starting from the Main screen:
• Press the Scroll button (12) until <P.14> appears
.
• Press the Enter button (13).
Instruction book
42
2920 7101 41