Electrical characteristics
Model
Indoor unit
MFC
Power cable
Signal cable
Hz
Voltage
Minimum
Maximum
L ≤ 20m
L ≤ 50m
Grounded
CMV-V56Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V71Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V80Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V90Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V100Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V112Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V125Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V140Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
CMV-V160Q/HR1-C
50Hz
220-240V
198
264
15
2*2.5mm
2
2*4.0mm
2
2.5mm
2
2*0.75 mm
2
Notes:
1)
Minimum: Permitted minimum operating voltage, lower than this value may damage the system
2)
Maximum: Permitted maximum operating voltage, higher than this value may damage the system
3)
MC: Minimum Current (A)
4)
MFC: Maximum Fuse Current (A)
5)