APPENDIX C: Register listing for unit with Vari Pro room controller
When controlling fan coil with the room controller, use the following register
map.
Table 4: Register listing for unit with Vari Pro room controller
Vari Pro User Interface Register Map v 1.4
Modbus RTU RS485
Baudrate: 9k6, 19k2, 38k4
Parity: None, odd, even
Description
Read/
Write
Min.
Max.
Unit
Note(s)
Write register 16 bit integer register
4x00001
Application state
W
1 = Stand-by (OFF)
2 = Normal
3 = Away
4 = Flush (set cool & heat
100%)
5 = Stopped
10 = Test mode (allow cool/
heat without fan)
4x00003
Fan speed control
W
0 = OFF, 1–3 = Speed,
4 = Auto
4x00004
Room set point,
Normal
W
x10C
4x00005
Room set point,
Away
W
x10C
Read register 16 integer register
3x00004
Application state
R
0 = Init
1 = StandBy
2 = Normal,
3 = Away
4 = Flush
10 = Test
3x00006
Current fan control
R
0
4
0 = OFF, 1–3 = Speed,
4 = Auto
3x00007
Room temperature
R
°C
x10
3x00008
Current room set
point
R
°C
x10
3x00009
Current fan speed
R
0
100
%
3x00010
Cooling output
R
0
100
%
3x00011
Heating output
R
0
100
%
Copyright © 2020. All rights reserved.
42 (45)
N02119031 Rev. A