2. Use supports to mount the unit to the ceiling. Make sure that you use
supports that are suitable for the installation site and the ceiling material.
Note! The supports must be strong enough for the max. weight (GIANT 700 = 115
kg / GIANT 1300 = 185 kg) of the unit.
Note! Do not hoist the unit from pipe joints, valves, or the condensation water basin.
You can hoist the unit to the ceiling by using a lift, or similar.
WARNING
Use a hoist that is rated to handle the weight of the unit.
a. If you use threaded bars for supporting the unit, you must secure the joint
between the threaded bar and the support with locknuts and washers.
b. Make sure that the bars are attached tightly to the ceiling and they do not
come off.
3. Make sure that the distance between the unit and the ceiling is at least 30
mm.
≥ 30 mm
M8
M8
EN
Copyright © 2020. All rights reserved.
17 (40)
N02541445 Rev. A
GIANT Vari – Installation, Operation, and Maintenance Manual