- 53 -
[List of Calc setting parameters]
Parameter
Function
Default
Set value
Kind
Select calculation type
None
None, Root (square root), LOGe (natural logarithm),
LOG10 (common logarithm), INT (integration), Humidity,
COM.Input (data communications input), MUL
(arithmetic 1), DIV (arithmetic 2), High-Peak (max value),
Low-Peak (min value), Average, Power (exponent),
Formula, BrokenLine (broken line approximation)
Decimal point
Set decimal point position for result
*
0 to 3
Form.No.
Specify formula No. when
“Formula”
is selected for Kind
*
- (None), 1 to 12
Seg.Table No.
Specify broken line table No. when
“BrokenLine” is selected for Kind
*
- (None), 1 to 6
CH.X
Specify CH for X data used by each
calculation
*
- (None), 1 to 6
CH.Y
Specify CH for Y data used by each
calculation
*
- (None), 1 to 6
Const.A
Set calculation constant A when
arithmetic 1 or 2 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
Const.B
Set calculation constant B when
arithmetic 1 or 2 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
Const.C
Set calculation constant C when
arithmetic 1 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
Const.D
Set calculation constant D when
arithmetic 1 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
[Start]
Set calculation start time
Calculation is waited until set time
(data during the waiting period is
invalid).
*
- (None), 00 : 00 to 23 : 59
When
“-“ is set, following operations are performed.
Integration: Operated by external reset
Formula: Operated at power-on or immediately after
setting is made
[Interval]
Set calculation interval
For calculations using integration,
integration value is reset at set
intervals.
*
- (None), 00 : 00 to 24 : 59
Setting
“-“ or “00 : 00” disables interval.
TimeUnit
Unit of integration time
*
Hour, Min, Sec
INT-Reset
Set integration reset method for
calculations using integration
*
None (reset not performed), Interval (specified interval),
EX (All) (all reset by remote contact), EX (individual reset
by remote contact)
INT-Reset.EX
Specify remote contact No. used
when
“EX” is selected for "INT-Reset"
*
- (None), 1 to 5