[DB600] General instruction manual
- 139 -
General specifications
Rated power voltage
100-240V AC(±10%)
24V AC
/
DC(±10%)
Rated power supply frequency
50
/
60Hz(±2%)
Maximum power consumption:
100 to 240V AC (without option)
DB630
100V AC
4VA
240V AC
5VA
DB650
100V AC
4VA
240V AC
6VA
DB670
100V AC
4VA
240V AC
6VA
100 to 240V AC (with option)
DB630
100V AC
5VA
240V AC
7VA
DB650
100V AC
7VA
240V AC
10VA
DB670
100V AC
9VA
240V AC
12VA
24V AC/DC (without option)
DB630
24V AC
3VA
24V DC
2W
DB650
24V AC
4VA
24V DC
3W
DB670
24V AC
4VA
24V DC
3W
24V AC/DC (with option)
DB630
24V AC
4VA
24V DC
3W
DB650
24V AC
7VA
24V DC
5W
DB670
24V AC
8VA
24V DC
6W
Countermeasure
against power
failure
Store setting contents in non-volatile memory.
(Rewrite: 1 million times)
Insulation
resistance
Between the primary and secondary terminals
20MOhm or more (500V DC)
* Primary terminal:
Power terminal
(100 to 240V AC),
EV1 to 4 output
terminals (relay output),
ON-OFF pulse output
terminal (relay output),
ON-OFF servo output
terminal (M3, M2, M1)
Secondary terminal: Power terminal
(24V AC/DC),
all terminals except
primary terminals
Withstand voltage
Between the primary and secondary terminals
1500V AC (1 minute)
* See "Insulation resistance" for the primary
and secondary terminals.
Exterior material
Front: Fire-retardant acrylonitrile butadiene
styrene/polycarbonate (UL94V-0)
Case: Fire-retardant polycarbonate (UL94V-2)
Color
Gray
Mounting
Panel mounting type
External
dimensions
DB630
48(W)×48(H)×88(D)
(Depth from panel surface is 80)
DB650
48(W)×96(H)×73(D)
(Depth from panel surface is 65)
DB670
96(W)×96(H)×73(D)
(Depth from panel surface is 65)
Weight
DB630
(Without option)
Approx. 120g
(With option)
Approx. 135g
DB650
(Without option)
Approx. 150g
(With option)
Approx. 230g
DB670
(Without option)
Approx. 240g
(With option)
Approx. 330g
Terminal screw
M3.0
Engineering port
DB630
At the bottom of the case
DB650
At the top of the case
DB670
At the top of the case
Reference operating condition
Ambient temperature
23°C±2°C
Ambient humidity
55%RH±5% (no condensation)
Power voltage
100V AC±1%
Power supply
frequency
50
/
60Hz±0.5%
Mounting orientation
Backward/forward ±3°, laterally ±3°
Installation height
Below 2000m
Vibration
0 m/s
2
Shock
0 m/s
2
Installation condition
Single panel mounting (space required
around)
Wind
None
External noise
None
Warm-up time
At least 30 minutes
Normal operating condition
Ambient temperature
-10 to 50°C
(-10 to 40°C for close installation)
Maximum ambient humidity (ambient temperature -10 to 31°C)
90% RH (no condensation)
Maximum ambient humidity (ambient temperature 31 to 50°C)
90 to 50% RH (no condensation)
* Decreases linearly from 90% RH at 31°C, or to 50% RH at 50°C.
Minimum ambient
humidity
20%RH
Power voltage:
100 to 240V AC
90 to 264V AC
24V AC/DC
21.6 to 26.4V AC/DC
Power supply
frequency
50/60Hz±2%
Mounting orientation
Backward/forward ±10°, laterally ±10°
Installation height
Below 2000m
Vibration
0 m/s
2
Shock
0 m/s
2
Installation condition
Panel mounting (space above and below)
External noise
None
Ambient temperature
variation ratio
10°C/hour or less
Transport condition
Ambient temperature
-20 to 60°C
Ambient humidity
5 to 95% RH (no condensation)
Vibration
4.9m/s
2
or less (10 to 60Hz)
Shock
392m/s
2
or less (under factory packing
condition)