[DB600] General instruction manual
- 143 -
Screen
Item
Setting range
Default
MODE 5 Input type
□□□
□
: Thermocouple B
(0.0 to 1820.0°C)
□□□
□
: Thermocouple R
(0.0 to 1760.0°C)
□□□
□
: Thermocouple S
(0.0 to 1760.0°C)
□□□
□
: Thermocouple N
(0.0 to 1300.0°C)
□□□
: Thermocouple K1 (-200.0 to 1370.0°C)
□□□
: Thermocouple K2 (-200.0 to 500.0°C)
□□□
□
: Thermocouple E (-200.0 to 900.0°C)
□□□
□
: Thermocouple J (-200.0 to 1200.0°C)
□□□
□
: Thermocouple T (-200.0 to 400.0°C)
□□□
□
: Thermocouple U (-200.0 to 400.0°C)
□□□
□
: Thermocouple L (-200.0 to 900.0°C)
: Thermocouple W-WRe5-26
(0.0 to 2310.0°C)
: Thermocouple W-WRe26
(0.0 to 2310.0°C)
: Thermocouple PlatinelII
(0.0 to 1390.0°C)
□
: Thermocouple PtRh40-20
(0.0 to 1880.0°C)
: Thermocouple Au-Pt (0.0 to 1000.0°C)
□
: ±20mV
(-20.00 to 20.00mV)
: ±100mV
(-100.0 to 100.0mV)
□□
□
: ±5V
(-5.000 to 5.000V)
□□
: ±10V
(-10.000 to 10.000V)
□
□
:
Pt 100_1
(-200.0 to 850.0°C)
□
□
:
Pt 100_2
(-200.0 to 200.0°C)
□
:
JPt 100_1
(-200.0 to 649.0°C)
□
:
JPt 100_2
(-200.0 to 200.0°C)
□
:
Pt 50
(-200.0 to 649.0°C)
□□□
Unit
: °C (Celsius)
: mV
□
: V
□□□
Measuring range L
Within the range (* See input type)
Measuring range H
Linear decimal point
: No decimal point
: 1 digit after decimal point
□□
to
: 4 digits after decimal point
□
Linear scale zero
to
□□□
Linear scale span
to
Sensor correction
to
[°C]
□□
Digital filter
to
[sec]
□□□
SV limiter L
to
[°C]
SV limiter H
to
[°C]
Display decimal point
: No decimal point
: 1 digit after decimal point
□□
to
: 4 digits after decimal point
□
MODE 6 Pulse cycle
to
[sec]
□□□
Feedback zero
to
[%]
□□□
Feedback span
to
[%]
□
Feedback dead band
to
[%]
□□□
PID dead band/
output dead band
to
[%]
□□□
Control action
: Heating control
: Cooling control
Output preset
to
[%]
□□
Output variation limiter L
to
[%]
Output variation limiter H
to
[%]
□
PV abnormal output
to
[%]
□□□
Preset manual
to
[%]
□□□
Operation on power ON
: READY status/program
operation RESET
: Operation right before
previous power-OFF
Control algorithm
: Position PID control
: Velocity PID control
MODE 7 Output 2 control system
□□
: PID control
: Split control
□□
Output 2 P
: Two-position control
to
[%]
□□□
Output 2 I
to
[sec]
□□□
Output 2 D
to
[sec]
□□□
Output 2 gap
to
[%]
□□□
Output 2
PID dead band/
output dead band
to
[%]
□□□
Output 2 control action
: Heating control
: Cooling control
Output 2 output preset
to
[%]
□□□
Split Direct
to
[%]
□□□
Split Reverse
to
[%]
□
Output 2 pulse cycle
to
[sec]
□□□
Output 2 output limiter L
to
[%]
□□□
Output 2 output limiter H
to
[%]
□
Output 2 variation limiter L
t
o
[%]
Output 2 variation limiter H
to
[%]
□
Output 2 preset manual
to
[%]
□□□
Screen
Item
Setting range
Default
MODE a Communication
protocol
□□
:
MODBUS RTU
:
MODBUS ASCII
:
Private
□□
Communication
function
□□
: Host communication
: Digital transmission
: Digital remote input
□□
Instrument No.
to
□□□□
Communication
transmission rate
□
:
4800bps
□
:
9600bps
:
19200bps
:
38400bps
□
Communication
character
: 7-bit/even parity/stop bit 1
: 7-bit/even parity/stop bit 2
: 7-bit/odd parity/stop bit 1
: 7-bit/odd parity/stop bit 2
: 8-bit/no parity/stop bit 1
: 8-bit/no parity/stop bit 2
: 8-bit/even parity/stop bit 1
: 8-bit/even parity/stop bit 2
: 8-bit/odd parity/stop bit 1
: 8-bit/odd parity/stop bit 2
□□
Digital transmission
type
□
: Digital SV transmission
□
: Digital PV transmission
□
: Digital output 1 transmission
: Digital output 2 transmission
: Digital FB transmission
□□□
Digital transmission
interval
: 100msec interval
: 200msec interval
□
: 1
00m
sec interval
□
MODE b Transmission type
□
: SV transmission signal output
□
: PV transmission signal output
□
: Output 1 transmission signal output
: Output 2 transmission signal output
: FB transmission signal output
□□□
Transmission scale zero
to
[°C]
Transmission scale span
to
[°C]
MODE c Remote/local
switching
: Local SV operation
: Remote SV operation
Remote SV shift
to
[°C]
□□
Remote filter
to
[sec]
□□□
Tracking at
switch to local
: Function OFF
□
: Tracking ON
□□
Remote scale zero
to
[°C]
Remote scale span
to
[°C]
Cascade γ
to
□□
Cascade β
to
□□□
MODE d External input 1
□□
: Function OFF
: RUN/READY switch
: AUTO/MANUAL switch
: Preset manual
: Timer 1
: Timer 2
: Alarm event reset
□
: Execution No. selection 1 (Bit0)
□
: Execution No. selection 2 (Bit1)
□
: Execution No. selection 4 (Bit2)
□
: Execution No. selection 8 (Bit3)
: Program/constant value
operation switch
□
: Program operation RUN/STOP
□
: Program operation ADVANCE
: Program operation RESET
: Program pattern 1 (Bit0)
: Program pattern 2 (Bit1)
: Program pattern 4 (Bit2)
□□
External input 2
External input 3
External input 4
External input 5
External input 6
External input 7
MODE t Model No. (1) (2) (3) (4) (5)
See model code
Model No. (6) (7) (8) (9) (10)
Model No. (11) (12) (13) (14)
Key lock
□□
: No key lock
: Operation parameter keys
locked
□□
: All parameter keys locked
□□
Operation initial screen
□□
: PV/SV display screen
: PV/step time display screen
□
: PV/output 1 display screen
: PV/output 2 display screen
□□□
Operation screen SV
display
□□□
: SV display
: Blank display
: Multi display
Bar display
□□
: No display
□□
: Output 1 value display
□
: Output 2 value display
□□□
: CT measured value display
□□□
: FB measured value display
□
: Step remaining/elapsed time
display
□□
Parameter storing
: Backup function OFF
□
:Backup function ON
□□
Parameter initialization
□
: No initialization
: Initialization executed
□□