[DB600] General Instruction Manual
MODE 4
- 85 -
□
□□
▲
SEL
↑
↓▼
SEL
Event extension
function
(Event No. 1 to No. 4)
Sets the event extension function.
The function becomes effective when the event mode is alarm event (excluding
heater disconnection alarm/timer alarm/FAIL alarm).
"
□□
"
No extension function (normal alarm)
"
□
"
Event standby
"
□
"
Event keep
"
"
Event standby/keep
The display appears only when "Event No. (MODE4)" is set to "
" to
"
".
Use the [
], [
] and [ENT] keys to set the event extension function.
Set the event No. at "Event No. (MODE4)".
□□
▲
SEL
↑
↓▼
SEL
Event dead band
(Event No. 1 to No. 4)
Sets the event dead band.
The function becomes effective when the event mode is alarm event (excluding
timer alarm and FAIL alarm).
"
□□
"
to
"
"
0.00 to 200.00 [%]
The display appears only when "Event No. (MODE4)" is set to "
" to
"
".
Use the [
], [
] and [ENT] keys to set the event dead band.
Use the [>] key to move the cursor to the right digit.
Set the event No. at "Event No. (MODE4)".
▲
SEL
↑
↓▼
SEL
Event output phase
(Event No. 1 to No. 9)
Sets the event output phase.
"
"
Normal output phase
Output OFF while event OFF
Output ON while event ON
"
"
Reverse output phase
Output ON while event OFF
Output OFF while event ON
This display is available for the specification with event output.
Use the [
], [
] and [ENT] keys to set the event output phase.
Set the event No. at "Event No. (MODE4)".
"Reverse output phase" does not function while the instrument is turned OFF or
start-up screen is displayed.
5-6-3
Event mode
In addition to the alarm event output such as higher/lower limit alarm, output can be made when the timer
function or instrument is in abnormal condition, or depending on the operating condition. Assign the events
to the event output terminals.
When "Event No. (MODE4)" is set to No. 1 to 4, assignment is available for both the alarm and status
events.
When event No. 5 to 9 is set, assignment is only available for status event.
See the section 6-3 for the alarm event type and 6-4 for the status event.
5-6-4
Event extension function
The event extension function can be set when "Event No. (MODE4)" is set to No. 1 to 4, and "Event mode
(MODE4)" is set to alarm event (excluding heater disconnection alarm/timer alarm/FAIL alarm).
Event standby
The event standby operation does not make an immediate output in an event activation status. Once out
of the event activation range, the event output becomes effective.
The event standby operation is performed in the following situations.
Constant value operation
On power ON, when changing alarm value in executing SV value, switching execution No. selection
for constant value operation, alarm status and READY to RUN.
Program operation
In changing switching RESET to RUN and executing ADVANCE
.