INST.No.INE-863B KR2S
【
Communication Interface
】
Instruction Manual
-99-
8-4-7
File-related-parameter
R/W … R: READ, W: WRITE
Reference
number
Applied
function code
R/W
Content
Detail
47207
03
06
16
R
W
W
File 1
Data recording
cycle
0: 0.1 sec., 1: 0.2 sec., 2: 0.5 sec., 3: 1 sec., 4:
2 sec., 5: 3 sec., 6: 5 sec., 7: 10 sec., 8: 15
sec., 9: 20 sec., 0: 30 sec., 11: 1 min., 12: 2
min., 13: 3 min., 14: 5 min., 15: 10 min., 16: 15
min., 17: 20 min., 18: 30 min., 19: 60 min.
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47208
03
06
16
R
W
W
File 1 Start trigger
0: Key, 1: Alarm, 2: Contact input
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47209
03
06
16
R
W
W
File 1 Start
condition 1
ASCII 2 digits
47208: The start trigger of File 1 is;
1: In case of alarm, 01 to Alarm output
2: In case of contact input, 01 to Number of
remote contact
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47210
03
06
16
R
W
W
File 1 Start
condition 2
Number of pre-trigger: 10-increment for 0 to
950
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47211
03
06
16
R
W
W
File 1 End trigger
0: Same as Start trigger, 1: Count
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47213
03
06
16
R
W
W
File 1 End
condition
Count: 10-increment for 0 to 30000
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47221
03
06
16
R
W
W
Storing type
0: Binary (setting information existed), 1: CSV
2: CSV(continue)
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47222
03
06
16
R
W
W
CF saving cycle
0: None, 1: 1 min., 2: 2 min., 3: 3 min., 4: 5
min., 5: 10 min., 6: 20 min., 7: 30 min., 8: 60
min.
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47223
03
06
16
R
W
W
Data type
0: Sample, 1: Average, 2: Maximum, 3:
Minimum, 4: Maximum/minimum
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47224
03
06
16
R
W
W
File size
0: Automatic (same as at present)
1: 10 min., 2: 15 min., 3: 20 min., 4: 30 min.,
5: 60 min., 6: 2 hours, 7: 3 hours, 8: 4 hours,
9: 6 hours, 10: 8 hours, 11: 12 hours,
12: 24 hours, 13: 1 week, 14: 1 month
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47231
03
06
16
R
W
W
Storing file
directory 1, 2
ASCII 2 digits
Error code: 01H, 02H, 03H, 09H, 11H, 12H
47232
03
06
16
R
W
W
Storing file
directory 3, 4
ASCII 2 digits
Error code: 01H, 02H, 03H, 09H, 11H, 12H
Summary of Contents for KR2S
Page 2: ...INST No INE 863B KR2S Communication Interface Instruction Manual ...
Page 124: ...INST No INE 863B KR2S Communication Interface Instruction Manual ...
Page 125: ...INST No INE 863B KR2S Communication Interface Instruction Manual ...
Page 126: ...INST No INE 863B KR2S Communication Interface Instruction Manual ...
Page 127: ...INST No INE 863B KR2S Communication Interface Instruction Manual ...