4.4 RS-422A, RS-485 Connections
This paragraph describes the method of connecting the RS-422/485 communications interface to the
personal computer by using the line converter (Model SC8-10: sold separately). Since the line converter
and the personal computer use three control signals of Send, Receive and Signal ground only, the wiring
processing inside the connectors is necessary in the same way as in RS-232C connections.
[For details, read the instruction manual for line converter (Model SC8-10: sold separately).]
RD
SD
SG
RDA
RDB
SDA
SDB
1
2
3
4
5
6
7
8
1 2 3 4 5
6 7 8 9
SDA SDB
RDA
RDB
SDA SDB
RDA RDB
SDA SDB
RDA
RDB
SE3000
series field
scanner
SE3000
series field
scanner
SE3000
series field
scanner
Line converter
9-pin connector
(The wiring processing inside the
connector is necessary.)
9-pin connector
(The wiring processing inside the
connector is necessary.)
Termination resistor 100
Ω
SE3000
series field
scanner
1 2 3 4 5
6 7 8 9
Line converter
Termination resistor 100
Ω
In case of RS-422A
In case of RS-485
RD
SD
SG
RDA
RDB
SDA
SDB
1
2
3
4
5
6
7
8
Communications Cable
RZ-CRA1
□□
Communications Cable
RZ-CRA2
□□
Communications Cable
RZ-CRS6
□□
Communications Cable
RZ-LEC
□□□
Communications Cable
RZ-CRS6
□□
Communications Cable
RZ-LED
□□
SDA
SDB
RDA
RDB
SE3000
series field
scanner
SDA
SDB
RDA
RDB
SE3000
series field
scanner
SDA
SDB
RDA
RDB
Receiving
data
SDA
SDB
Sending
data
RDA
RDB
Inside circuit
Please do not connect
SG line to FG terminal
or the protective conductor
terminal of instrument.
Caution!
Please do not connect
SG line to FG terminal
or the protective conductor
terminal of instrument.
Caution!