-36-
R/W
……
R:READ
,
W:WRITE
Reference No.
Applicable
function
code
R/W
Description Details
40133
03
06
16
R
W
W
CH1 Level 1 Alarm
Mode
0 : No programming, 1 : H, 2 : L, 3 : U, 4 : D
5 : B, 6 : S
Error code : 01H, 02H, 03H,11H,12H
40134
03
06
16
R
W
W
CH1 Level 1 Alarm
Alarm Value
-9999 to 30000(Scale decimal point used for decimal place)
Error code : 01H, 02H, 03H,11H,12H
40135
03
06
16
R
W
W
CH1 Level 1 Alarm
Output Relay
ASCII 2 digits (space code available for 1st digit)
01 to No. of alarm outputs, 00H : No programming
Error code : 01H, 02H, 03H,11H,12H
40137
03
06
16
R
W
W
CH1 Level 1 Alarm
Reference CH
ASCII 2 digits (space code available for 1st digit)
01 to No. of channels, 00H: No programming *Valid for differential alarm
Error code : 01H, 02H, 03H,11H,12H
40138
03
06
16
R
W
W
CH1 Level 2 Alarm
No. of Samples
ASCII 2 digits (space code available for 1st digit)
01 to 09, 00H : No programming *Valid for rate-of-change alarm
Error code : 01H, 02H, 03H,11H,12H
40141
03
06
16
R
W
W
CH1 Level 2 Alarm
Mode
0 : No programming, 1 : H, 2 : L, 3 : U, 4 : D
5 : B, 6 : S
Error code : 01H, 02H, 03H,11H,12H
40142
03
06
16
R
W
W
CH1 Level 2 Alarm
Programming
Value
-9999 to 30000(Scale decimal point used for decimal place)
Error code : 01H, 02H, 03H,11H,12H
40143
03
06
16
R
W
W
CH1 Level 2 Alarm
Output Relay
ASCII 2 digits (space code available for 1st digit)
01 to No. of alarm outputs
、
00H : No programming
Error code : 01H, 02H, 03H,11H,12H
40145
03
06
16
R
W
W
CH1 Level 2 Alarm
Reference CH
ASCII 2 digits (space code available for 1st digit)
01 to 09, 00H : No programming *Valid for differential alarm
Error code : 01H, 02H, 03H,11H,12H
40146
03
06
16
R
W
W
CH1 Level 2 Alarm
No. of Samples
ASCII 2 digits (space code available for 1st digit)
01 to 09, 00H : No programming *Valid for rate-of-change alarm
Error code : 01H, 02H, 03H,11H,12H
40149
03
06
16
R
W
W
CH1 Level 3 Alarm
Mode
0 : No programming, 1 : H, 2 : L, 3 : U, 4 : D
5 : B, 6 : S
Error code : 01H, 02H, 03H,11H,12H
40150
03
06
16
R
W
W
CH1 Level 3 Alarm
Alarm Value
-9999 to 30000(Scale decimal point used for decimal place)
Error code : 01H, 02H, 03H,11H,12H
40151
03
06
16
R
W
W
CH1 Level 3 Alarm
Output Relay
ASCII 2 digits (space code available for 1st digit)
01 to No. of alarm outputs, 00H : No programming
Error code : 01H, 02H, 03H,11H,12H
40153
03
06
16
R
W
W
CH1 Level 3 Alarm
Reference CH
ASCII 2 digits (space code available for 1st digit)
01 to No. of channels, 00H : No programming *Valid for differential alarm
Error code : 01H, 02H, 03H,11H,12H
40154
03
06
16
R
W
W
CH1 Level 3 Alarm
No. of Samples
ASCII 2 digits (space code available for 1st digit)
01 to 09, 00H : No programming *Valid for rate-of-change alarm
Error code : 01H, 02H, 03H,11H,12H