SETTINGS OF SWITCHES
Before mounting and connections, set the switch No. 1 (SW.1) at the front of instrument and the switch No. 2
(SW.2) up side. Make sure to confirm the settings even if you use the defaults.
3.1 Instrument number
3.2 Communications port
SW1-6
OFF(default) ON
COM (default)
ENG
SW1-1 SW1-2
SW1-3
SW1-4
SW1-5
Number
OFF OFF OFF OFF OFF
1
(default)
ON OFF OFF OFF OFF
1
OFF ON OFF OFF OFF
2
ON ON OFF OFF OFF
3
OFF OFF ON OFF OFF
4
ON OFF ON OFF OFF
5
OFF ON ON OFF OFF
6
ON ON ON OFF OFF
7
OFF OFF OFF ON OFF
8
ON OFF OFF ON OFF
9
3.3 Communications type
OFF ON OFF ON OFF
10
ON ON OFF ON OFF
11
OFF OFF ON ON OFF
12
ON OFF ON ON OFF
13
OFF ON ON ON OFF
14
ON ON ON ON OFF
15
OFF OFF OFF OFF ON
16
ON OFF OFF OFF ON
17
OFF ON OFF OFF ON
18
ON ON OFF OFF ON
19
OFF OFF ON OFF ON
20
SW2
ON OFF ON OFF ON
21
Front side
Back side (Default)
OFF ON ON OFF ON
22
(Terminals side)
(DIN rail side)
ON ON ON OFF ON
23
RS232C RS422A/485
ON OFF OFF ON ON
25
OFF ON OFF ON ON
26
For the connection with the BR, change to
ON ON OFF ON ON
27
RS422A/485.
OFF OFF ON ON ON
28
ON OFF ON ON ON
29
OFF ON ON ON ON
30
ON ON ON ON ON
31
Note) Don't duplicate the settings of each instrument.
Mounting place of SW.1
Change by a small screwdriver.
Mounting place of SW.2
422A/485
DIN rail side
Up side of
instrument
232C
Change with a sharp tipped material.
Terminal side
The engineering port is used for the
configuration by the parameter programming
software package (PASS – Separate
purchase is required.). Communications with
PC cannot be executed when changed to the
engineering port.
Engineering port
For parameters and other settings by the parameter
programming software package (PASS – Separate
purchase is required.), it is necessary to change to
the engineering port.