200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
37
selection
0: Protection(The terminal is closed before
power-on and operation is not allowed)
1: No protection(The terminal is closed before
power-on to allow operation)
F1-01 Directly start frequency
0.00
~
10.00Hz
0.00Hz
√
F1-02
Start frequency holding
time
0.000s
~
32.000s
0.000s ×
F1-03 Start DC brake current
0
~
150%
0% ×
F1-04 Start DC brake time
0.000s
~
32.000s
0.000s ×
F1-05 Stop function selection
The single digit : Normal stop mode selection
0: Decelerate to stop
1: Free stop
Ten digits: Reserved
Hundred digits: Jog stop mode selection
0: Decelerate to stop
1: Free stop
0000
√
F1-06
Stop braking start
frequency
0.00Hz
~
F0-05
0.00Hz
√
*
F1-07
Deceleration stop brake
waiting time
0.000s
~
32.000s
0.000s
√
*
F1-08
Deceleration stop DC
braking current
0
~
150%
0%
√
*
F1-09
Deceleration stop DC
braking time
0.0s
~
32.000s(When it is 0.0s, no DC braking)
0.000s
√
*
F1-10
Power-off restart waiting
time
0.0s
~
32.000s
2.000s
√
F1-11
Momentary stop power
generation judgment
voltage
70.0%
~
110.0%(standard bus voltage)
90.0%
√
F1-12
Momentary stop power
generation deceleration
enable
0: Disable
1: Enable
0
√
F1-13
Momentary stop restart
enable
0: Disable
1: Enable
0
√
F1-14
Reverse rotation control
prohibited (invalid
during torque control)
0: Reversion allowed
1: Reversion forbidden
0 ×
F1-15
Carrier association
adjustment selection
Unit: Carrier adjustment related temperature
0: Disabled
1: Enabled
Ten units: Carrier adjustment associated load
001
√