200 Series General Purpose Vector AC Drive Chapter 5 Functional Parameter Simple List
45
F5-15 FDT lag detection value 000.0%
~
100.0%(FDT Electric Level)
5.0%
√
*
F5-16 FDT torque level value 0.0%
~
250.0%
100.0%
√
F5-17
FDT torque level
detection lagged value
0.0%
~
100.0%(FDT Electric Level)
5.0%
√
F5-18 FM1output
selection 00: Operating frequency: 0
~
Maximum output
frequency
01: Setting frequency: 0
~
Maximum output
frequency
02: Bus voltage: 0
~
2 times standard bus
03: Output current: 0
~
2 times ac drive rated
current
04: Output voltage: 0
~
1.2 times ac drive
rated voltage
05: Operating speed: 0
~
rotation speed
corresponding to maximum frequency06:
Output power: 0
~
2 times motor rated power
07: Setting torque: 0
~
2 times ac drive rated
current
08: Output torque: 0
~
2 times ac drive rated
current
09: PID setting: 0.0
~
100.0%
10: PID feedback: 0.0
~
100.0%
11: Analogue V1 input value: 0.00
~
10.00V
12: Analogue V2 input value: 0.00
~
10.00V/ 0
~
20mA
13: HDI high speed pulse: 0.00
~
100.00kHz
14: Specify output percentage F5-35: 0.0
~
100.0%
0
√
F5-19 FM2 output selection
3
√
F5-20
HDO high speed pulse
output selection
1
√
F5-21
FM1 output lower limit
percentage
0.0
~
100.0%
0.0%
√
F5-22
FM1 lower limit
corresponding output
0.00
~
10.00V
0.00V
√
F5-23
FM1 output upper limit
percentage
0.0
~
100.0%
100.0%
√
F5-24
FM1 upper limit
corresponding output
0.00
~
10.00V
10.00V
√
F5-25
FM2 output lower limit
percentage
0.0
~
100.0%
0.0%
√
F5-26
FM2 lower limit
corresponding output
0.00
~
10.00V
0.00V
√
F5-27
FM2 output upper limit
percentage
0.0
~
100.0%
100.0%
√