7.2 AC Wire Connections
Configuration of inverter with different Utility Grid Systems
CPS grid-tied PV Inverter can be installed with the following type of utility grid
systems by 2 wire or 3 wire AC cables, and with a ground cables as
illustrated in the table below.
Figure 7.2.1: Utility grid systems
Acceptable PV Systems for CPS grid-tied PV Inverter:
For 208V and 240V 3-phase delta grid system, a 3-phase delta configuration
can be used by the 2 AC wires connected to the Point of Common Coupling
(PCC) L1 and L2 location and a ground cable connected to the L2 location as
shown in the above table.
For 240V split grid system, a split-phase configuration can be used by 3 AC
wires connected to the PCC's L1, L2 and N location and a ground cables
connected to the N location as shown in the above table.
For 277V 3-phase Y grid system, a wye type configuration can be used by 2
AC wires connected to L1 and N locations with a ground cables connected to
the N location as shown in the above table.
For 208Y /120V 3-phase Y grid system, a wye type configuration can be used
by 3 AC wires connected to L1, L2, and N with a ground cable connected to
the N location as shown in the above table.
WARNING
Configuration of utility grid connections is required to be completed
by a licensed technician or electrical contractor. Ensure the correct
sized AC cables are used!