Copyright CPS America Co., Ltd. Page 59
9.2 Clean the LCD Display
If the screen of the LCD display and the LED indicators are dusty and not
readable, please use a piece of damp cloth to clean the surface.
9.3 Install or Replace the DC/AC fuse
Insulation Protection
The insulation gloves should be worn during wiring, replacing
fuses and installing components.
ELECTRIC SHOCK
There is a risk of electric shock from the energy stored in the
capacitors. Therefore, it is necessary not to remove the top cover
of wiring box until 3 minutes after DC/AC disconnect switch is
turned off.
It is necessary to turn off the external DC/AC breakers if they
exist.
Otherwise, it is important to disconnect all the PV modules
and AC utility connections before the service of fuse
replacement. The PV Inverter must be disconnected from all
sources of power supply. Refer service to only qualified service
personnel.
IMPORTANT
The selection of the DC fuses must follow the instructions
outlined in chapter f. DC protection of section 6.2 within the
manual.
A)
Remove the fuse cover from the fuse holders as shown in figure 9.3.1:
Figure 9.3.1: Remove the fuse cover