background image

Table

 

1

 

Key

 

technical

 

parameters

        

JKF8

 

smart

 

low

-

voltage

 

reactive

 

power

 

automatic

 

compensation

 

controller

 (

hereinafter

 

referred

 

to

 

as

 

controller

is

 

designed

 

for

 

reactive

 

power

 

compensation

 

in

 

low

 

voltage

 

power

 

distribution

 

systems

By

 

compounding

 

controlling

 

of

 

physical

 

variables

 (

reactive

 

power

 

and

 

power

 

factor

), 

the

 

product

 

enables

 

automatic

 

capacitor

 

switching

power

 

factor

 

improvement

 

and

 

line

 

reactive

 

power

 

loss

 

reduction

It

 

is

 

easy

 

for

 

operation

 

and

 

reliable

with

 

complete

 

functions

 

and

 

strong

 

anti

-

interference

 

capability

The

 

product

 

complies

 

with

 

JB

/

T9663

 

standard

 

and

 

can

 

correctly

 

display

 

grid

 

power

 

factor

 

under

 

harmonic

 

environment

.

Use

 

Purpose

1

 

        Type

 

Key

 

and

 

Definitions

 

Key

 

Technical

 

Parameters

2

 

Rated

 

frequency

60Hz

no

 

this

 

option

 

for

 

default

 

50Hz

 

Rated

 

voltage

220VAC

240VAC

380VAC

440VAC

 

Output

 

circuit

 

specification

6

12

 

Product

 

design

 

serial

 

number

  

Control

 

of

 

physical

 

variables

compound

 

Low

-

voltage

 

reactive

 

compensation

 

controller

JK

    

F

    

8

  

    

    

  

Environm

ental

 

condition

s

Ambient

 

temp

(℃)

-

25

℃~+

70

℃ 

Hot

 

and

 

humid

 

atmospheric

 

conditions

50

relative

 

humidity

 

at

 +

40

℃; 

up

 

to

 

90

at

 +

20

℃;

Altitude

2000m

, (

take

 

ventilation

heat

 

dissipation

 

and

 

anti

-

condensation

 

measures

 

for

 

altitude

 

above

 

2000m

)

Pollution

 

class

/

installation

 

category

Free

 

from

 

hazardous

 

gases

 

and

 

vapors

conductive

 

or

 

explosive

 

dusts

and

 

strong

 

mechanical

 

vibration

Functions

Control

 

strategy

Compound

 

control

 

of

 

reactive

 

power

 

and

 

power

 

factor

ensuring

 

reliable

 

switching

 

under

 

low

 

load

 

and

 

preventing

 

resonance

 

during

 

switching

Display

 

code

Non

-

polarized

 

current

Self

-

identifying

 

of

 

current

 

polarity

no

 

direction

 

requirement

 

for

 

IS1

 

and

 

IS2

 

sampling

 

lines

.

Undervoltage

 

protection

Automatically

 

removes

 

capacitor

 

banks

 

in

 

operation

 

level

 

by

 

level

 (

in

 

5

 

seconds

when

 

grid

 

voltage

 

is

 

lower

 

than

 

0

.

78UN

 

and

 

displays

 

voltage

 

value

U

Overvoltage

 

protection

Automatically

 

removes

 

capacitor

 

banks

 

in

 

operation

 

level

 

by

 

level

 (

in

 

5

 

seconds

when

 

grid

 

voltage

 

higher

 

than

 

overvoltage

 

threshold

 

and

 

displays

 

voltage

 

value

.  

U

Undercurrent

 

protection

Automatically

 

removes

 

capacitor

 

banks

 

in

 

operation

 

level

 

by

 

level

 (

in

 

5

 

seconds

and

 

lock

-

up

 

capacitor

 

adding

 

when

 

the

 

secondary

 

signal

 

of

 

the

 

current

 

transformer

 

is

 

lower

 

than

 

150

A

1

JKF8 SeriesSmart Low-Voltage Reactive Power Compensation Controller

01

Summary of Contents for JKF8 Series

Page 1: ...Standard JB T 9663 2013 NO 2021 01 JKF8 Series Smart Low Voltage Reactive Power Compensation Controller User Instructions ...

Page 2: ...maintenance 2 Installation in any damp condensed phase environment with inflammable and explosive gas is forbidden 3 When the product is being installed or maintained the power must be switched off 4 You are prohibited from touching the conductive part when the product is operating ...

Page 3: ...heric conditions 50 relative humidity at 40 up to 90 at 20 Altitude 2000m take ventilation heat dissipation and anti condensation measures for altitude above 2000m Pollution class installation category Free from hazardous gases and vapors conductive or explosive dusts and strong mechanical vibration Functions Control strategy Compound control of reactive power and power factor ensuring reliable sw...

Page 4: ...external sampling current transformer 5 1200 set ratio factory preset 60 means 300 5 Delay time setup 5 120 seconds factory preset 30 seconds Setup mode Full automatic mode display code 1 no need to set adding threshold and removing threshold Manual setup mode display code 0 adding threshold and removing threshold need to be set manually Adding threshold setup Full automatic mode capacity of the s...

Page 5: ...ly and fixing of the controller Figure 2 Product installation and fixing Table 2 Description of dynamic parameters Code Definitions Unit Description I Current A Use approximate value when measured value exceeds display range for example displays E13 for 1260A U Voltage V Displays measured voltage Q Reactive power kvar Use approximate value when measured value exceeds display range for example disp...

Page 6: ...se A for current phase B and C for voltage phase B for current phase A and C for voltage phase C for current phase A and B for voltage Terminal COM is the relay common terminal for the output of group 1 12 of the controller Terminals 1 12 are used for output control of the contactors of the compensation circuits of the capacitor display If the system voltage is 3 phase 380V and the coil voltage of...

Page 7: ...dd capacitors level by level until the grid reactive power demand is lower than reactive power threshold Qs and the power factor is not bigger than target power factor when the power factor of the grid exceeds target power factor the leading indicator will start flashing the system will automatically remove capacitor banks in operation level by level in 5 seconds 3 3 2 Parameter setup 3 3 2 1 See ...

Page 8: ...ts the value of each circuit is 15 20 30 30 30 30 30 30 then the set Qs value should be minimum capacity of 15 kilovar F 1 SET 15 Manual switching In automatic mode press and hold SET menu key for 3 seconds to enter manual mode Press adjustment display key to add one group of capacitor bank press parameter display key to remove one group of capacitor bank Circular self testing In automatic mode pr...

Page 9: ...re disconnecting the power supply of the cabinet 4 1 4 Short circuit the secondary side of the sampling current transformer before removing or replacing the JKF8 controller to prevent open circuit of the current transformer Remove the short circuit line after reinstalling the controller 4 2 Analysis and troubleshooting of faults 3 3 3 Preparation and inspection before use 1 Before using the capaci...

Page 10: ... adding capacitors the power factor remains almost the same The installation position of the current transformer is wrong the primary current is not included in the cabinet Take total current sampling current load current capacitor current which means the primary line of the cabinet is connected after the sampling transformer 6 No matter what load the controller always displays leading the power f...

Page 11: ... be disposed of according to the industrial waste treatment process or be sent to the recycling station for assortment dismantling and recycling according to local regulations 5 Environmental Protection 09 JKF8 SeriesSmart Low Voltage Reactive Power Compensation Controller ...

Page 12: ...JKF8 SeriesSmart Low Voltage Reactive Power Compensation Controller DR J03 JKF8 Series Smart Low Voltage Reactive Power Compensation Controller JB T 9663 2013 10 ...

Page 13: ...JKF8 SeriesSmart Low Voltage Reactive Power Compensation Controller 11 ...

Page 14: ...JKF8 Series Smart Low Voltage Reactive Power Compensation Controller User Instructions ...

Reviews: