The form has the following fields:
MQTT Settings
•
MQTT Port
–
The MQTT listen port for receiving incoming messages. Default: 1883.
BACnet Server Settings
•
Port
–
The port for the BACnet IP connection. Default: 47808
•
Device Instance
–
The Device instance for this BACnet server object.
•
Device Name
–
The Device name for this BACnet server object.
Fill out the fields and click the ‘Save’ button to save the settings.
Note: If either the MQTT Port or BACnet Port settings were changes, please reboot the gateway for
the changes to take effect. For more information on how to reboot the gateway, please refer to
section
4.3 Completing the Configuration
After saving the settings and possibly rebooting the device, the gateway is ready to accept Eniscope
data. As the gateway received data, it will auto-configure the mapped BACnet objects. You can view
the full list of BACnet objects in the reports page. For more information about the reports page,
please refer to section
5.1 Reading Data Using HTML/Web Browser
Use the reports page to confirm that the expected data points exist. Finally save the configuration and
reboot the gateway.