COMUNICATION PORTS
The Gateway uses the following ports for communication over the ethernet port.
Protocol
Port
Notes
HTTP
TCP 80
Web server, not configurable.
Syslog
UDP 514
Can be disabled.
FTP
TCP 21
Can be disabled, requires Firmware Update
MQTT
TCP 1883
Configurable.
BACnet IP
UDP 47808
Configurable.
Table 3-1 - Communication Ports
WIRING CONNECTIONS
The BEST Gateway only uses the ethernet port for communication. Use a standard ethernet patch
cable to connect the gateway to the network. For more information on changing the IP Address of the
gateway, please refer to section
6.5 Change the Gateway IP Address