Image 4.6 –Pulse API Configuration Successful
Continue adding more data points.
4.3 Saving the Configuration
After adding all the Rib Devices to the configuration, return to the System Page by browsing to the
following IP Address: http://ip/bin/system/ where ip is the IP Address of the Gateway.
To Save the Database, click the ‘Save Database’ link , then click the Ok button when prompted. You will
see some XML saying that the Save was successful. Click the ‘Back’ button in the web browser.
Now Reboot the Gateway by Clicking the ‘Reboot System’ link. When prompted, click the Ok button.
Link is highlighted in the image below
Image 4.7 – System Actions Page – Reboot System
The Gateway will take 30-45 seconds to reboot.
Note:
The Gateway must be rebooted after configuration because the BACnet IP Objects are generated
during the boot cycle.