36
Temperature 1zero
0002
Used to adjust the temperature zero of the controller. When the
terminal of the controller temperature sensor is connected to the
resistance corresponding to -20 ℃, adjust this value and adjust the
temperature to -20 ℃.
Temperature calibration.
Temperature2zero
0002
Note: MAM6080 controller, this parameter is standby.
Temperature3zero
0002
Temperature4zero
0002
Temperature5zero
0002
Temperature6zero
0002
Pressure1zero
0002
When the supply pressure value is less than the set value, the
display pressure value is 0.00. It is used to prevent the gas supply
pressure sensor from drifting on
the zero point.
Pressure2zero
0002
When the pressure value 2 is less than the set value, thepressure
valueis0.00.itisusedtopreventthezero
drift of the gas supply pressure sensor.(standby)
P1 pressure range
(MPa)
01.60
Set the measuring range of the gas supply pressure
sensor of the controller.
P2 pressure range
(MPa)
01.60
Set the controller pressure 2 sensor ranges. (Standby).
Phase sequence
protection value
(
V
)
000.9
When the voltage value detected by the three-phase phase
sequence detection circuit is lower than the value set here, the
phase sequence error is reported. When this value is set to 0,
phase sequence protection is disabled.
Lack of sequence
protection value
(
V
)
000.0
When the detected phase breaking voltage is lower than the
value set here, the phase sequence is wrong. When this value is set
to 0, the phase sequence protection function is disabled.
Note: MAM6080 controller, this parameter is standby.
Motor electricity
change
020
Motor frame rated current percent 5.
Fan motor electricity
change
001
Fan motor rated current percent 2.5.
Spare
Used for controller factory debugging.
5.1.8 Joint control parameters
The joint control parameters are used to set up the related functions of the joint control.
Before the user modifies the joint control parameters, the password of the joint control
parameters should be verified.
The main functions and functions are shown in the table below:
Summary of Contents for Quan Wei
Page 1: ...TaiWan QuanWei Screw type air compressor Using and Maintenance Instructions ...
Page 12: ...8 ...
Page 81: ...77 ...
Page 82: ...78 8 2 2 QWL 15A 20A 8 2 3 QWL 30A 40A ...
Page 83: ...79 8 2 4 QWL 50A 60A ...
Page 84: ...80 8 2 5 QWL 75A 100A ...
Page 85: ...81 8 2 6 QWL 150A 175A ...
Page 86: ...82 9 0 Circuit diagram ...
Page 87: ...83 9 1 MAM 860 880 Circuit diagram 9 2 MAM 890 Circuit diagram ...
Page 88: ...84 9 3 MAM 6080 Circuit diagram ...
Page 89: ...85 Screw Air Compressor operation record tale ...