63
QuanWei MACHINERY (Jiang Su)
B
phase
electricity
input standard current value, the controller automatically calculates the
current coefficient and saves it to complete the current calibration.
2. After the calibration is completed, the standard current value is
automatically returned to zero.
Coefficient
1.000
When calibrating the current, the input coefficient.
Controller display current value = sampling value
×
coefficient
Current
electricity
***.*A
Current real-time electricity value
Fan motor
C
phase
Standard
electricity
0000
1. It is used to calibrate the C phase current of wind motor. After
input standard current value, the controller automatically calculatesthe
current coefficient and saves it to complete the current calibration.
2. After the calibration is completed, the standard current value is
automatically returned to zero.
Coefficient
1.000
When calibrating the current, the input coefficient.
Controller display current value = sampling value
×
coefficient
Current
electricity
***.*A
Current real-time electricity value
Standard temperature
000
0℃
1. It is used to calibrate the exhaust temperature. After input the
standard temperature value, the controller automatically calculatesthe
temperature coefficient and saves it to complete the temperature
calibration.
2. After the calibration is completed, the standard temperature value
is automatically returned to zero.
Coefficient
1.000
Input coefficient when calibrating temperature.
The controller displays the temperature value (sampling temperature
value-zero point)
×
coefficient
Zero
0010
℃
Compensate for hardware zero deviation.
Current temperature
****
℃
Current real-time temperature value.
Standard pressure
00.00
MPa
1. Used to calibrate standard pressure. After input of standard pressure
value, the controller automatically calculates pressure coefficient and
saves it to complete pressure calibration.
After calibration is completed, the standard pressure value is
automatically returned to zero.
Coefficient
1.000
When calibrating pressure, input coefficient.
Controller display pressure value = sampling pressure value
×
coefficient.
Zero
00.02
MPa
When the gas supply pressure is less than the value set here, it is
displayed as 0.00MPa.
Current pressure
**.**
MPa
Current real-time pressure value.
Standard voltage
0000
V
1. It is used to calibrate the standard voltage. After the standard
voltage value is input, the controller automatically calculates the
standard voltage coefficient and saves it to complete the calibration of
the standard voltage.
Summary of Contents for Quan Wei
Page 1: ...TaiWan QuanWei Screw type air compressor Using and Maintenance Instructions ...
Page 12: ...8 ...
Page 81: ...77 ...
Page 82: ...78 8 2 2 QWL 15A 20A 8 2 3 QWL 30A 40A ...
Page 83: ...79 8 2 4 QWL 50A 60A ...
Page 84: ...80 8 2 5 QWL 75A 100A ...
Page 85: ...81 8 2 6 QWL 150A 175A ...
Page 86: ...82 9 0 Circuit diagram ...
Page 87: ...83 9 1 MAM 860 880 Circuit diagram 9 2 MAM 890 Circuit diagram ...
Page 88: ...84 9 3 MAM 6080 Circuit diagram ...
Page 89: ...85 Screw Air Compressor operation record tale ...