23
Chloride Active
UK
Submenu
Functionality
1.1 Acoustic Alarm
Activation or deactivation of acoustic alarm (buzzer)
1.2 Manual Battery Test
Performs a battery test when this option is selected
MENU 1.- CONTROL
Submenu
Functionality
2.1 UPS Status
Displays global UPS Status (operation mode, faults, warnings…)
2.2 Input/Output Status
Displays input and output values (voltage, frequency, load…)
MENU 2.- ST
A
TUS
Submenu
Functionality
3.1 Language
Language selection (English, Spanish, Italian, French, Portuguese, German)
3.2 Output Voltage
Selects nominal output voltage (200V, 208V, 220V, 230V or 240V)
MENU 3.- SETUP
Functionality
Displays the last
fi
ve events (faults, warnings…) stored by the UPS and the runtime when they happened. These
stored events are explained in section 4.2.2.2
MENU 4.- LOGGING
Functionality
Displays power rating, serial number of the UPS,
fi
rmware version and current unit runtime
MENU 5.- ABOUT
Submenu
Functionality
6.1 Frequency Converter
Enables or disables this operation mode (please check 4.1.5 and 4.4.6 for more details)
6.2 Output Frequency
Selects nominal output frequency: 50Hz or 60Hz (only frequency converter mode)
6.3 Manual Bypass
Forces the UPS to bypass mode and vice-versa
6.4 Controllable Outlet 1 Manual
Setting
Switches on/off outlet 1 (1st group of output controllable sockets)
6.5 Controllable Outlet 2 Manual
Setting
Switches on/off outlet 2 (2nd group of output controllable sockets)
6.6 Controllable Outlet 1 Level
Selects remaining battery capacity level (75%, 50%, 25% or 0%) below which
outlet 1 (1st group of output controllable sockets) automatically switches off
6.7 Controllable Outlet 2 Level
Selects remaining battery capacity level (75%, 50%, 25% or 0%) below which
outlet 2 (2nd group of output controllable sockets) automatically switches off
6.8 Cold Start
Enables/disables this functionality (start-up without mains power)
6.9 Auto Re-Start
Enables/disables this functionality (automatic start-up after autonomy time has
fi
nished and upon mains power comeback)
6.10 ECO Mode
Enables or disables this operation mode (please check 4.1.4 and 4.4.5 for more details)
6.11 Site Wiring Fault
Enables/disables this functionality (detection of input phase-neutral inversion)
6.12 Automatic Battery Test
Sets automatic battery test interval (daily, weekly, monthly…)
6.13 External Battery Capacity
Selects external battery capacity (Ah) for special / customized con
fi
gurations,
in steps of 9Ah up to 250Ah (value selected pressing scroll-down button)
6.14 External Charger Selection
Selects the number of external battery chargers (available as accessory for
special / customized con
fi
gurations) connected, from 1 to 3
6.15 Pre-alarm Level Selection
Selects the remaining battery capacity level (75%, 50%, 25% or 0%) below
which the “Battery Low” signal is activated
6.16 Protocol selection
Communication protocol selection for particular advanced applications
MENU 6.-
ADV
ANCED OPTIONS
Menu 6 includes options for advanced user and, consequently, access to this menu is protected with a password
(a certain combination of keys).
When this menu is selected, you will be asked to press the code keys (PRESS CODE KEYS (CHECK U.
MANUAL)). Correct code keys combination is:
Press ESC button and release it - press scroll-down button and release it - press ENTER button and release it.
If this sequence and combination of keys is followed, access to the menu will be granted and the display will
show ACCESS GRANTED ATTENTION! If not, an error message will show (ACCESS DENIED WRONG
CODE KEYS).
Summary of Contents for 2000
Page 1: ...UK ...
Page 2: ...1 Chloride Active UK ...
Page 3: ...1 Chloride Active ENGLISH DEUTSCH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS UK DE E FR I P ...
Page 38: ...36 UK Chloride Active 945044 066 Tower models Rack Tower models ...
Page 76: ...74 DE Chloride Active 945044 066 Tower Modelle Rack Tower Modelle ...
Page 114: ...112 E Chloride Active 945044 066 Equipos torre Equipos rack torre ...
Page 152: ...150 FR Chloride Active 945044 066 Matériels colonnes Matériels rack colonnes ...
Page 190: ...188 I Chloride Active 945044 066 Apparecchi tower Apparecchi rack tower ...
Page 228: ...226 P Chloride Active 945044 066 Equipamentos torre Equipamentos rack torre ...
Page 234: ...235 Chloride Active P www chloridepower com 945044 066 Ed 2 Feb 08 ...