Do not allow the liquid to get inside the UPS.
Clean the outside of the UPS housing by wiping with a dry or a slightly wet cloth.
8. Troubleshooting
If a problem occurs despite the high reliability of the device, please review the following table before
calling the service center.
- Is the UPS plugged into a correctly working outlet ?
- Has a fuse blown or the protector on the rear panel tripped?
- If the problem persists, please note the following information when you call for service:
A. Information about the device (model, order number, serial number from type plate, date of pur-
chase and date of installation)
B. Full description of problem (which load is connected, does the problem occur regularly or sporadi-
cally, etc.)
24
945012.066
REV: 16/03/01
Operating Manual
Problem
Possible Cause
Corrective Action
No power from mains.
Check the status of the electricity
supply
No signaling
No alarm
(the
UPS
is
disconnected)
The protection switch has been
activated
Reset. If the problem persists,
consult your after sales service.
Problem
Possible Cause
Corrective Action
Indicator light is not on
but there is power from
the mains.
The input protection switch has
reacted.
Reset. If the problem persists,
consult your after sales service.
Overload
Reduce the load. (Eliminate the
protected equipment until the
anomaly disappears)
The acoustical ALARM
light is on
Overheating
Reduce the ambient temperature
Batteries not fully charged.
Batteries are defective
Residual capacity time
is less than the value
indicated.
efective charging system
Charge batteries (see 3.1 start-
up) and check the autonomy
time.
If the problem persists, consult
your after sales service.