44
The UPS only requires that the air filters be cleaned on periodical bases and that the area around the UPS is clean and free from
dust and debris. When the batteries expire, these must be replaced by the appropriate battery specifications. Exhausted
accumulator batteries are classified as “harmful toxic waste” and as such, the law demands that they be disposed of by an
authorized recycling center.
Periodic maintenance should be performed on the UPS and batteries. Chloride Power Protection recommends the UPS be
maintenance at least two time per year and batteries up to four times per year.
CHLORIDE POWER PROTECTION Customer Service Center is fully equipped to deal with such batteries, in accordance with the
Law and with the greatest respect for the environment.
The typical battery life cycle is 3 to 5 years, at an ambient temperature of 77 F, but is also dependent on the frequency and duration
of mains failures.
A battery test should be carried out periodically (6 to 12 months) in order to ascertain the general condition of the batteries.
PRECAUTIONS
During maintenance, disconnect the battery trays so that no more than eight batteries are connected in series.
All safety and handling instructions shall be carefully observed.
Qualified personnel may only remove the access panels.
Watches, rings, chains and any other metal objects must be removed before working on the batteries
Rubber gloves
must
be used.
Insulated tools
only
must be used.
An insulated mat must be placed in front of the battery cabinet before any operation is carried out thereon.
Never work alone
. Ensure the presence of a person able to give assistance in case of accident.
Chapter
8
MAINTENANCE